{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6016-7MC16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6016-7MC16","canonicalUrl":"https://aoctrl.com/siemens/5SV6016-7MC16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6016-7MC16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-MCB combination, 1P+N, C-curve, 6 kA Icn, 230 V AC, integrated metering, DIN rail, IP20/IP40, 18 mm wide.","salesMarkdown":"## What this SENTRON AFDD-MCB combination does The built-in metering measures voltage, current, active/reactive/apparent power, line frequency, power factor, temperature, switching cycles, operating hours, and trip events, displayed on the front panel. Rear-side protection is IP20; the front face is IP40. The design is halogen-free and silicon-free, and it meets IEC 61373 for shock and vibration resistance — relevant for rail or mobile applications. ## Metering accuracy and standards The metering function is seamless (continuous) and complies with IEC 61557-12, IEC 62053-22, and IEC 62053-23 for error limits. Voltage and current accuracy is 0.5 %; active power accuracy is 1 %. The unit also includes a frequency meter, ammeter, voltmeter, wattmeter, and reactive power meter — all integrated into the 1-MW footprint, eliminating the need for a separate panel meter on that circuit.","metaTitle":"Siemens 5SV6016-7MC16 SENTRON AFDD+MCB, 1P+N, C-curve, 6 kA","metaDescription":"Siemens SENTRON 5SV6016-7MC16 AFDD-MCB combination, 1P+N, C-curve, 6 kA Icn, 230 V AC. Integrated metering (A, V, W, Hz, VAR). DIN rail, IP20/IP40. Current production. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","Height":"90 mm","Ammeter":"Yes","Maximum":"75 °C","Minimum":"-40 °C","Rear Side":"IP20","Voltmeter":"Yes","Wattmeter":"Yes","For Shocks":"IEC 61373","Halogen-Free":"Yes","On The Front":"IP40","Silicon-Free":"Yes","Design Of Pole":"1P+N","Frequency Meter":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"AFDD-MCB combination","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Reactive Power Meter":"Yes","Design Of The Product":"Compact unit","Protocol Is Supported":"wireless protocol","Standards For Error Limits":"based on IEC61557-12, IEC62053-22, IEC62053-23","For Measured Variable Current":"0.5 %","For Measured Variable Voltage":"0.5 %","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"C","Type Of Measured Value Detection":"seamless","For Measured Variable Active Power":"1 %","Status Display Of The Measured Data":"voltage, current, active power, apparent power, reactive power, active energy, line frequency, power factor, temperature, switching cycles, operating hours, tripping, warnings","according to EN 60898-1 rated value":"6 000 A","For Measured Variable Apparent Power":"1 %","For Measured Variable Reactive Power":"1 %","according to IEC 60947-2 rated value":"6 000 A","Guideline Via Radio-Controlled System":"2014/53/EU","Switching Function Short-Term Delayed":"No","For Measured Variable Electrical Energy":"1 %","Measurable Line Frequency Initial Value":"45 Hz","Type Of Voltage Of The Operating Voltage":"AC","Frequency With Radio Transmission Maximum":"2 483.5 MHz","Frequency With Radio Transmission Minimum":"2 400 MHz","Measurable Line Frequency Full-Scale Value":"60 Hz","Measuring Category For Voltage Measurement":"CATIII according to IEC 61010-2-030","Measuring Procedure For Current Measurement":"TRMS","Measuring Procedure For Voltage Measurement":"TRMS","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Apparent Power Consumption Of The Power Supply":"0.4 VA","For Environmental Sinusoidal Oscillation Check":"IEC 60068-2-6","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"2.1 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e2939b7046519e3be2f5a5be6711c6b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1445927&mlfb=5SV6016-7MC16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV6016-7MC16/alternatives.json"},"ai":{"faq":[{"question":"What is the 5SV6016-7MC16's width and depth for panel layout?","answer":"Width is 18 mm (1 modular unit), depth is 68.5 mm, height is 90 mm. It snaps onto a DIN rail."},{"question":"What compliance documentation does Siemens provide for this AFDD-MCB?","answer":"The unit is designed to IEC 61557-12, IEC 62053-22, and IEC 62053-23 for metering accuracy, and IEC 61373 for shock/vibration. It is halogen-free and silicon-free. The breaking capacity is tested to EN 60898-1 at 6 kA."},{"question":"Where can I buy the 5SV6016-7MC16 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6016-7MC16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6016-7MC16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}