{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6316-7KK20","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6316-7KK20","canonicalUrl":"https://aoctrl.com/siemens/5SV6316-7KK20","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6316-7KK20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-RCBO, 230 V AC, 1P+N, C-curve, 20 A, 30 mA Type A, 6 kA, compact 1 MW unit.","salesMarkdown":"The Siemens SENTRON 5SV6316-7KK20 is a compact AFDD-RCBO — an arc-fault detection device combined with a residual-current circuit breaker in a single 1-module-wide unit. It protects a 1P+N circuit at 230 V AC, 20 A rated current, with a 30 mA Type A residual-current trip and C-curve overcurrent characteristic, breaking capacity rated at 6 kA per IEC 60898-1 and IEC 60947-2. Depth is 68.5 mm, installation depth 70 mm — enough clearance for a standard 70 mm deep enclosure with the conductors dressed behind. Any mounting position works; supply cord entry position is also unrestricted. Accepts supplementary add-on devices via the product extension interface. Spring-cage terminals accept 0.2–2.5 mm² solid or ferruled stranded; strip length 8 mm avoids whiskers under the cage. Listed as current production. This is a standard catalogue item from the SENTRON family, not a phase-out line. No LTB windows or successor cross-references apply. C-curve tripping characteristic (magnetic release at 5–10× In) suits mixed resistive-inductive loads like lighting, socket outlets, and small appliances — not motor starting. Power loss per pole is 2.65 W at rated current — factor that into thermal derating if the enclosure is tightly packed.","metaTitle":"Siemens 5SV6316-7KK20 SENTRON AFDD-RCBO, 1P+N, C, 20 A, 30 m","metaDescription":"Siemens SENTRON 5SV6316-7KK20 arc-fault detection RCBO. 1P+N, 230 V AC, 20 A, 30 mA Type A, 6 kA. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","title":"5SV6316-7KK20","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"AFDD-RCBOele 230V, 6kA, 1P+N, C, 20A Compact (1MW)","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Design Of The Product":"Compact unit","Residual Current Type":"A","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"C","Tripping Fault Current Rated Value":"30 mA","according to EN 60898-1 rated value":"6 000 A","according to IEC 60947-2 rated value":"6 000 A","Switching Function Short-Term Delayed":"No","operational current at AC rated value":"20 A","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","In The Event Of Electrical Arcs In Series With The Load Maximum":"20 A","In The Event Of Electrical Arcs In Series With The Load Minimum":"2 A","In The Event Of Electrical Arcs In Parallel With The Load Maximum":"500 A","In The Event Of Electrical Arcs In Parallel With The Load Minimum":"50 A","power loss [W] for rated value of the current at AC in hot operating state per pole":"2.65 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/393b7acaa895388baf9c183cd7c91855.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108737&mlfb=5SV6316-7KK20"},"ai":{"faq":[{"question":"Who supplies 5SV6316-7KK20 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is published here."},{"question":"What compliance documentation does this brand provide for 5SV6316-7KK20?","answer":"The SENTRON brand supplies this unit as halogen-free and silicon-free. It is rated IP20 with connected protective device and conductors, pollution degree 2, overvoltage category III. Standard IEC/EN certifications apply (IEC 60898-1, IEC 60947-2)."},{"question":"Will 5SV6316-7KK20 drop into a panel specified around 5SY4116-7CV without rewiring?","answer":"The 5SV6316-7KK20 is a 1-module-wide (18 mm) DIN-rail device with an installation depth of 70 mm. The 5SY4116-7CV is a standard MCB of the same width and DIN-rail footprint, so the mechanical fit and busbar slot are identical. However, the 5SV6316-7KK20 adds AFDD and RCBO functionality — it requires a neutral connection (1P+N) and has different internal wiring (the neutral must pass through the device). If the original panel only had a phase-only MCB with no neutral bar routed to that position, rewiring is needed. If the neutral is already present at the device position, it drops in without pa"}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6316-7KK20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6316-7KK20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}