{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6316-7KP20","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6316-7KP20","canonicalUrl":"https://aoctrl.com/siemens/5SV6316-7KP20","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6316-7KP20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV6316-7KP20, AFDD-RCBO combination, 230V AC, 20A, C-curve, 30mA Type A, 6kA, 1P+N, compact 1MW unit.","salesMarkdown":"The Siemens 5SV6316-7KP20 is a SENTRON AFDD-RCBO combination — an arc-fault detection device and residual-current circuit breaker in one 18 mm-wide, 1P+N compact unit. The 30 mA Type A RCD detects sinusoidal AC and pulsating DC residual currents, covering the majority of modern electronic loads. The arc-fault detection (AFDD) identifies series and parallel arcs: rated for series arcs from 2 A to 20 A and parallel arcs from 50 A to 500 A, which covers the range where a loose connection or damaged cable could otherwise cause a fire before the overcurrent or RCD element clears it. Snaps onto DIN rail (REG) and occupies one modular width (18 mm). Depth is 68.5 mm; installation depth allowance is 70 mm, so it fits standard 70 mm-deep distribution boards without the door clashing.","metaTitle":"Siemens 5SV6316-7KP20 SENTRON AFDD-RCBO, 20A C 30mA Type A,","metaDescription":"Siemens SENTRON 5SV6316-7KP20 AFDD-RCBO combination, 230V AC, 20A, C-curve, 30mA Type A RCD, 6kA breaking capacity per EN 60898-1. 1P+N, 18mm wide. Active production, available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Design Of The Product":"Compact unit","Residual Current Type":"A","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"C","Tripping Fault Current Rated Value":"30 mA","according to EN 60898-1 rated value":"6 000 A","according to IEC 60947-2 rated value":"6 000 A","Switching Function Short-Term Delayed":"No","operational current at AC rated value":"20 A","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","In The Event Of Electrical Arcs In Series With The Load Maximum":"20 A","In The Event Of Electrical Arcs In Series With The Load Minimum":"2 A","In The Event Of Electrical Arcs In Parallel With The Load Maximum":"500 A","In The Event Of Electrical Arcs In Parallel With The Load Minimum":"50 A","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.75 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1268830&mlfb=5SV6316-7KP20","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV6316-7KP20/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV6316-7KP20?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; we source through independent distribution channels and can quote against your required quantity and delivery window."},{"question":"What is 5SV6316-7KP20's listed depth and width?","answer":"Depth is 68.5 mm (installation depth 70 mm) and width is 18 mm (one modular unit). Height is 90 mm. These dimensions allow it to fit standard 70 mm-deep distribution boards and occupy one DIN-rail slot."},{"question":"What compliance documentation does Siemens provide for 5SV6316-7KP20?","answer":"The part is designed to EN 60898-1 and IEC 60947-2 for breaking capacity, and carries IP20 protection with connected conductors. As a SENTRON product, it is CE-marked and RoHS-compliant; full declarations and certificates are available from Siemens upon request."},{"question":"Will 5SV6316-7KP20 drop into a panel specified around 5SY4116-7CV without rewiring?","answer":"No — the 5SV6316-7KP20 is an AFDD-RCBO combination (arc-fault plus RCD plus MCB in one unit), while the 5SY4116-7CV is a plain MCB. The wiring differs because the AFDD-RCBO requires a neutral connection and has different terminal assignments. The physical footprint is the same 18 mm width, but the circuit design must be reviewed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6316-7KP20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6316-7KP20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}