{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV8702-2KK","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV8702-2KK","canonicalUrl":"https://aoctrl.com/siemens/5SV8702-2KK","factsUrl":"https://aoctrl.com/api/mcp/products/5SV8702-2KK","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV8702-2KK, Type B summation current transformer, 60 mm internal diameter, 160 A rated operational current, 10 mA minimum residual current, IP20 terminals, plug-in connection.","salesMarkdown":"The Type B designation means it detects smooth DC residual currents in addition to AC and pulsed DC — essential for modern installations with variable-speed drives, UPS systems, or EV charging infrastructure where pure DC fault currents can blind standard Type A devices. The 60 mm ID lets you pass up to three main conductors (, L2, L3) plus neutral through the window, or a single busbar up to that diameter. The 160 A rated current sets the maximum continuous load the transformer can monitor without saturating; size the primary circuit so the full-load current stays at or below this figure. Minimum residual current detection starts at 10 mA, so the device can pick up very small leakage paths — useful for personnel protection or ground-fault monitoring in sensitive circuits. The rated surge voltage withstand is 8 kV, which covers the impulse category for 400/690 V distribution panels without additional surge suppression on the transformer itself. ## DIN-rail integration and wiring constraints Mounts on standard DIN rail; dimensions are 135 mm wide, 67 mm high, and 116.4 mm deep. The 116.4 mm depth is the key clearance dimension when the transformer sits behind a panel door or inside a shallow enclosure — check that the door clearance or back-panel depth exceeds this figure before committing the layout. Connection is via plug-in terminals rated for 6 x 0.75 mm² conductors, so secondary wiring to the RCD or evaluation unit uses small cross-sections. The maximum secondary wire length is 10 m; keep the run short to avoid voltage drop or noise pickup on the residual signal. Terminals are IP20 — suitable for dry indoor panels only. If the panel sits in an unconditioned space that drops below freezing or exceeds 55 °C, the transformer must be relocated or derated per the manufacturer's thermal curve.","metaTitle":"Siemens 5SV8702-2KK SENTRON Summation Current Transformer, T","metaDescription":"Siemens SENTRON 5SV8702-2KK Type B summation current transformer, 160 A rated, 60 mm ID, for AC/DC systems. Active lifecycle, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"116.4 mm","Width":"135 mm","Height":"67 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$163.83","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0ffa1a1748ccdbd4bc65e4daa29dea24.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=767561&mlfb=5SV8702-2KK","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV8702-2KK/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV8702-2KK","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV8702-2KK when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}