{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV8702-2KP","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV8702-2KP","canonicalUrl":"https://aoctrl.com/siemens/5SV8702-2KP","factsUrl":"https://aoctrl.com/api/mcp/products/5SV8702-2KP","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV8702-2KP Type B summation current transformer, 60 mm internal diameter, rated 160 A, 690 V AC, IP20, plug-in terminal.","salesMarkdown":"It is built for residual current monitoring in grounded and ungrounded networks, including systems with smooth DC fault currents — the Type B classification means it detects AC, pulsed DC, and smooth DC residual currents down to 10 mA minimum, which is critical for variable-speed drives, UPS systems, and EV charging infrastructure where standard Type A transformers would miss a pure DC fault. Rated 160 A continuous and 690 V AC at 50/60 Hz, with an 8 kV surge voltage rating — that covers most low-voltage distribution panels up to 690 V line-to-line. The 60 mm internal diameter passes three or four main conductors plus the PEN conductor through the window, typical for a 160 A feeder. The minimum residual current sensitivity of 10 mA allows use in applications requiring high-sensitivity earth leakage detection, such as medical IT systems or data centers. The metal shielding (noted in the description) reduces external magnetic field influence, improving measurement accuracy in crowded panels. The plug-in terminal accepts up to six conductors of 0.75 mm² each, making secondary wiring straightforward. The IP20 protection class is standard for indoor panel mounting — no special sealing needed. ## Deployment context The Type B rating makes it suitable for circuits with variable-speed drives, UPS systems, or any load that can generate smooth DC fault currents — standard Type A transformers would not detect a pure DC residual, so this part is the correct choice for modern electronic loads. The maximum wire length of 10 m between the transformer and the evaluation unit (RCD or relay) should be respected to avoid measurement errors.","metaTitle":"Siemens 5SV8702-2KP SENTRON Summation Current Transformer, T","metaDescription":"Siemens SENTRON 5SV8702-2KP Type B summation current transformer, rated 160 A, 60 mm ID, for AC/DC systems. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"116.4 mm","Width":"135 mm","Height":"67 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9b92eb2b956d1e896365f695f51e0d1e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=767562&mlfb=5SV8702-2KP","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV8702-2KP/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV8702-2KP","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV8702-2KP when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}