{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9313-1CN06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9313-1CN06","canonicalUrl":"https://aoctrl.com/siemens/5SV9313-1CN06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9313-1CN06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9313-1CN06, RCD-operated circuit breaker (RCBO), 1P+N, 6 A rated, 30 mA residual current, Type AC, tripping characteristic C, 18 mm width, IP20.","salesMarkdown":"The Siemens SENTRON 5SV9313-1CN06 is an RCD-operated circuit breaker (RCBO) combining overcurrent protection and residual current protection in a single 18 mm-wide module. Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2. For a domestic or light commercial distribution board fed from a transformer of typical impedance, that covers most fault scenarios downstream of a 63 A or smaller incoming device. The 1P+N design switches the line conductor and monitors the neutral; it occupies one modular width (18 mm) on the DIN rail, which is tight for an RCBO — most competitors need two widths for a combined device. ## Thermal derating and installation The 6 A rating holds at 30 °C ambient; at 40 °C it derates to 5.64 A, at 45 °C to 5.46 A, and at 55 °C to 5.04 A. In a crowded panel with multiple RCBOs side by side, the internal temperature rise reduces the usable current — plan the load at the derated figure for the expected cabinet ambient. Depth is 77 mm, installation depth 70 mm, height 90 mm.","metaTitle":"Siemens 5SV9313-1CN06 SENTRON RCBO, 6A, 30mA, Type AC, C-cur","metaDescription":"Siemens SENTRON 5SV9313-1CN06 RCD-operated circuit breaker, 6A rated, 30mA residual current, Type AC, C-curve, 1P+N, 18mm wide. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9313-1CN06","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 4.5 kA, 1P+N, Type AC, 30 mA, C-Char, In: 6 A, Un AC: 230 V, compact, China construction line","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"6 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Weight With Packaging":"135 g","at 30 °C rated value":"6 A","at 40 °C rated value":"5.64 A","at 45 °C rated value":"5.46 A","at 50 °C rated value":"5.22 A","at 55 °C rated value":"5.04 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.75 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=766272&mlfb=5SV9313-1CN06"},"ai":{"faq":[{"question":"What is the breaking capacity of this RCBO?","answer":"Rated breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2."},{"question":"What is the residual current sensitivity and type?","answer":"Tripping fault current is 30 mA, residual current type AC — detects sinusoidal AC fault currents."},{"question":"How does the 5SV9313-1CN06 compare to a standard MCB like the 5SL4106-7CC?","answer":"The 5SL4106-7CC is a Siemens SENTRON MCB with the same 6 A C-curve rating but no residual current protection — it occupies one modular width and protects only against overload and short circuit. The 5SV9313-1CN06 adds 30 mA RCD protection in the same 18 mm footprint, combining two functions where the MCB alone would need a separate RCCB. If your panel already has a shared RCD upstream, the MCB is sufficient; if you need per-circuit earth-fault protection, the RCBO is the direct fit."},{"question":"Where can I buy 5SV9313-1CN06 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9313-1CN06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9313-1CN06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}