{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9313-1CN16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9313-1CN16","canonicalUrl":"https://aoctrl.com/siemens/5SV9313-1CN16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9313-1CN16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9313-1CN16, RCD-operated circuit breaker, 2-pole 1P+N, AC type, 16 A rated, 30 mA residual, C-curve, 4.5 kA (EN 60898) / 5 kA (IEC 60947-2), 18 mm width.","salesMarkdown":"The 30 mA residual sensitivity (AC type) catches line-to-ground faults on sinusoidal AC waveforms — the standard for socket-outlet circuits and general-purpose final circuits where DC fault content isn't expected. Breaking capacity is rated 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — adequate for most domestic and light commercial sub-distribution boards where the prospective fault current at the point of installation stays under those thresholds. The 1P+N configuration switches the phase and switches the neutral, with the neutral pole opening simultaneously to ensure full isolation. IP20 protection applies once the board is installed with conductors connected — not rated for wet or dusty environments without an outer enclosure. The neutral conductor is switched internally, so no external neutral bar connection is needed on the load side — the outgoing neutral passes through the device.","metaTitle":"Siemens SENTRON 5SV9313-1CN16 RCD Circuit Breaker, 16 A, 30","metaDescription":"Siemens SENTRON 5SV9313-1CN16 RCD-operated circuit breaker, 16 A rated, 30 mA residual current, C-curve, 2-pole 1P+N, 4.5/5 kA breaking capacity. Current production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9313-1CN16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 4.5 kA, 1P+N, Type AC, 30 mA, C-Char, In: 16 A, Un AC: 230 V, compact, China construction line","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"230/240 V","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"135 g","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"4.5 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"5 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","operational current / at AC / rated value":"16 A","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=766274&mlfb=5SV9313-1CN16"},"ai":{"faq":[{"question":"Where can I buy the 5SV9313-1CN16 and get a price?","answer":"Sourced to order against an RFQ through independent distribution channels. Submit a request for quote (RFQ) for current availability and pricing — no stock count or price is published here."},{"question":"What are the key ratings of the 5SV9313-1CN16?","answer":"Rated operational current 16 A at 230/240 V AC, 50/60 Hz. Residual fault current 30 mA, AC type. Breaking capacity 4.5 kA per EN 60898 and 5 kA per IEC 60947-2. C-curve trip characteristic. 2-pole 1P+N with neutral switching."},{"question":"Will the 5SV9313-1CN16 fit in a panel designed for the 5SL6016-7KL?","answer":"Both are 18 mm wide (1 MW) DIN-rail devices, so the physical footprint is identical. The 5SV9313-1CN16 is an RCD-operated circuit breaker (RCBO) combining overcurrent and residual current protection, while the 5SL6016-7KL is a standard MCB without residual current detection. If the panel design requires only overcurrent protection, the 5SL6016-7KL is the simpler fit; if both overcurrent and ground-fault protection are needed on the same branch, the 5SV9313-1CN16 replaces the MCB+RCD pair in one unit. Verify the neutral switching arrangement — the 5SV9313-1CN16 switches the neutral internally,"}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9313-1CN16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9313-1CN16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}