{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9313-7CN10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9313-7CN10","canonicalUrl":"https://aoctrl.com/siemens/5SV9313-7CN10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9313-7CN10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9313-7CN10, RCBO, 2-pole 1P+N, 10 A rated, 30 mA Type A residual current, C-curve, 4.5 kA (EN 60898).","salesMarkdown":"The Siemens 5SV9313-7CN10 is a SENTRON RCBO — a residual-current-operated circuit breaker that packs overcurrent and earth-leakage protection into a single 18 mm-wide module. It's a 2-pole, 1P+N unit with a 10 A rated current and a 30 mA Type A residual-current trip. The C-curve characteristic means it handles moderate inrush (like small motors or lighting ballasts) without nuisance tripping. Rated breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — enough for most residential and light commercial distribution boards. ## Thermal derating — the real-world current At 40 °C it derates to 9.4 A, at 45 °C to 9.1 A, at 50 °C to 8.7 A, and at 55 °C to 8.4 A. If your panel runs warm — say, next to a drive or in a sunlit enclosure — size the load against the derated figure, not the label. Snaps onto DIN rail, takes one modular width unit (18 mm). Depth is 77 mm, height 90 mm, installation depth 70 mm. Mounting position is any — no restriction on upright or sideways. Touch protection is built in.","metaTitle":"Siemens 5SV9313-7CN10 SENTRON RCBO, 10 A, 30 mA, Type A, C-c","metaDescription":"Siemens SENTRON 5SV9313-7CN10 RCBO: 2-pole 1P+N, 10 A rated, 30 mA Type A residual current, C-curve, 4.5 kA (EN 60898). Active production. Available to order; request quote for pri","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9313-7CN10","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 4.5 kA, 1P+N, type A, 30 mA, C-Char, In: 10 A, Un AC: 230 V, compact, China construction line","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"135 g","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.4 A","at 45 °C / rated value":"9.1 A","at 50 °C / rated value":"8.7 A","at 55 °C / rated value":"8.4 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"4.5 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"5 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=766279&mlfb=5SV9313-7CN10"},"ai":{"faq":[{"question":"Where can I buy 5SV9313-7CN10 and how do I get a price?","answer":"We source this RCBO to order against an RFQ. Availability and current pricing are confirmed at quote time — submit a request and we'll respond with a firm price and lead time."},{"question":"What is 5SV9313-7CN10's rated current and residual trip?","answer":"It's rated 10 A with a 30 mA Type A residual-current trip, C-curve characteristic."},{"question":"What breaking capacity does 5SV9313-7CN10 have?","answer":"4.5 kA per EN 60898 and 5 kA per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9313-7CN10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9313-7CN10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}