{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9313-7CR16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9313-7CR16","canonicalUrl":"https://aoctrl.com/siemens/5SV9313-7CR16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9313-7CR16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9313-7CR16, RCD-operated circuit breaker, 1P+N, 16 A at 30 °C, C-curve, 4.5 kA per EN 60898, 18 mm width.","salesMarkdown":"The Siemens 5SV9313-7CR16 is a SENTRON RCD-operated circuit breaker — an RCBO that combines overcurrent protection and residual current detection in a single 18 mm-wide module. Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2, which covers most domestic and light commercial panel fault levels. The 1P+N design switches the line conductor only; the neutral is switched internally but not protected — standard for single-phase RCBOs in TN or TT systems. ## Mounting & integration Feed from either top or bottom — no mandatory orientation. Rated IP20 once installed in a distribution board with conductors connected, so it lives inside a closed enclosure, not exposed on the line side. ## Thermal derating Rated current drops with ambient temperature: 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, 13.76 A at 55 °C.","metaTitle":"Siemens 5SV9313-7CR16 SENTRON RCBO, 16A C-curve, 1P+N","metaDescription":"Siemens 5SV9313-7CR16 SENTRON RCD-operated circuit breaker, 16 A at 30 °C, C-curve, 1P+N, 4.5 kA per EN 60898. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9313-7CR16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 4.5 kA, 1P+N, type A, 30 mA, C-Char, In: 16 A, Un AC: 230 V, compact, China retail line","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"135 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.72 A","at 50 °C rated value":"14.24 A","at 55 °C rated value":"13.76 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.75 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629441&mlfb=5SV9313-7CR16"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV9313-7CR16?","answer":"Rated 4.5 kA per EN 60898 and 5 kA per IEC 60947-2, sufficient for most residential and light commercial distribution boards."},{"question":"Where can I buy 5SV9313-7CR16 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the width of 5SV9313-7CR16?","answer":"18 mm, one modular unit on standard DIN rail."},{"question":"Will 5SV9313-7CR16 drop into a panel specified around 5SL6120-7?","answer":"Both are 18 mm wide, 1-pole RCBOs on DIN rail, but 5SV9313-7CR16 is an RCD-operated circuit breaker (RCBO) while 5SL6120-7 is an MCB-only device. They are not drop-in replacements without rewiring the neutral and RCD function."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9313-7CR16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9313-7CR16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}