{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9313-7CR32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9313-7CR32","canonicalUrl":"https://aoctrl.com/siemens/5SV9313-7CR32","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9313-7CR32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole (1P+N), 32 A, 30 mA, Type A, C-curve, 4.5 kA per EN 60898, 5 kA per IEC 60947-2, 1 modular width (18 mm), IP20.","salesMarkdown":"The 5SV9313-7CR32: The 32 A rating at 30 °C is the base thermal current; at 40 °C it derates to 30.4 A, at 45 °C to 29.44 A, at 50 °C to 28.8 A, and at 55 °C to 27.84 A — so if the panel ambient runs above 30 °C, you need to account for that reduction when sizing the load. The 30 mA residual trip (Type A) catches sinusoidal AC fault currents plus pulsating DC faults, which covers most modern electronics and variable-speed drive leakage. Breaking capacity is 4.5 kA per EN 60898 (the standard for household and similar installations) and 5 kA per IEC 60947-2 (the industrial standard) — that's the fault current the device can safely interrupt without welding or exploding. Energy limitation class 3 means it limits through-energy to a low level during a short circuit, reducing arc-flash risk to downstream equipment. Snaps onto a DIN rail — 1 modular width (18 mm) — occupying a single slot.","metaTitle":"Siemens SENTRON 5SV9313-7CR32 RCBO, 2-pole, 32 A, 30 mA, C-c","metaDescription":"Siemens SENTRON 5SV9313-7CR32 RCBO, 2-pole (1P+N), 32 A rated, 30 mA residual current, C-curve, 4.5 kA (EN 60898). Active lifecycle. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9313-7CR32","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 4.5 kA, 1P+N, type A, 30 mA, C-Char, In: 32 A, Un AC: 230 V, compact, China retail line","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"32 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"135 g","at 30 °C / rated value":"32 A","at 40 °C / rated value":"30.4 A","at 45 °C / rated value":"29.44 A","at 50 °C / rated value":"28.8 A","at 55 °C / rated value":"27.84 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"4.5 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"5 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629444&mlfb=5SV9313-7CR32"},"ai":{"faq":[{"question":"Will 5SV9313-7CR32 drop into a panel specified around 5SU9304-1KK32 without rewiring?","answer":"Both are 1 modular width (18 mm) SENTRON RCBOs on the same DIN-rail footprint, so mechanical fit is identical. However, electrical ratings differ — verify that current rating, residual current, tripping curve, and breaking capacity match the circuit design before swapping. Rewiring is not needed if the terminal positions and supply orientation (top or bottom feed) are the same."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9313-7CR32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9313-7CR32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}