{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9313-7NK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9313-7NK16","canonicalUrl":"https://aoctrl.com/siemens/5SV9313-7NK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9313-7NK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, RCD-operated circuit breaker (RCBO), 2-pole, 16 A, C-curve, 30 mA Type A, 1 MW, IP20.","salesMarkdown":"The Siemens 5SV9313-7NK16 is a 2-pole RCD-operated circuit breaker (RCBO) from the SENTRON family, combining overcurrent protection and residual current protection in a single 18 mm wide module. The unit is designed for instantaneous operation — no intentional delay on the RCD side. The breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2. For a domestic or light commercial distribution board with a typical upstream fuse or MCB rated below 5 kA, this is adequate. The 30 mA trip threshold is standard for personnel protection (shock risk) in most residential and commercial circuits. Type A detection covers the common fault patterns in single-phase electronics loads — switch-mode power supplies, LED drivers, variable-speed drives — that generate pulsating DC leakage. ## Derating and installation Rated 16 A at 30 °C ambient, but derates to 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, and 13.76 A at 55 °C. In a crowded enclosure with elevated internal temperatures, size the load accordingly. It can be fed from either top or bottom, which simplifies panel wiring. Touch protection is built in.","metaTitle":"Siemens 5SV9313-7NK16 SENTRON RCBO, 2P, 16A, C-Curve, 30mA,","metaDescription":"Siemens 5SV9313-7NK16 SENTRON RCBO, 2-pole, 16 A rated, C characteristic, 30 mA residual current, Type A. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9313-7NK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 4.5 kA, 1P+N, type A, 30 mA, C-Char, In: 16 A, Un AC: 230 V, compact","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"135 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.72 A","at 50 °C / rated value":"14.24 A","at 55 °C / rated value":"13.76 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"4.5 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"5 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629447&mlfb=5SV9313-7NK16"},"ai":{"faq":[{"question":"What are the key ratings of the 5SV9313-7NK16?","answer":"It is a 2-pole RCBO rated 16 A, C-curve, 30 mA Type A residual current, with breaking capacities of 4.5 kA (EN 60898) and 5 kA (IEC 60947-2)."},{"question":"Where can I buy the 5SV9313-7NK16?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 5SV9313-7NK16?","answer":"The part is halogen-free and silicon-free. It carries an IP20 protection class and is designed to IEC 60898 and IEC 60947-2 standards. Specific RoHS, REACH, and UL declarations are typically available from Siemens upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9313-7NK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9313-7NK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}