{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-0PK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-0PK10","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-0PK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-0PK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-0PK10, RCBO, 2-pole (1P+N), 10 A, B-curve, 6 kA, Type AC, instantaneous, 230/240 VAC, 18 mm wide, IP20.","salesMarkdown":"Rated 10 A at 230/240 VAC with a B tripping characteristic, it handles general-purpose lighting and receptacle circuits where fast magnetic trip is needed for short-circuit protection. Type AC fault-current detection covers sinusoidal AC residual currents, which is the standard for general-purpose circuits without electronic loads generating pulsed DC faults. Thermal derating is published: 10 A at 30 °C, 9.4 A at 40 °C, 8.7 A at 50 °C, and 8.4 A at 55 °C. Width is 18 mm (1 width unit), depth 77 mm, height 90 mm. Installation depth 70 mm. Mounts in any position on standard DIN rail. Supply connects from below (bottom feed). Touch protection is built in. The part is silicon-free, which matters for potting or conformal-coating compatibility in harsh environments.","metaTitle":"Siemens SENTRON 5SV9316-0PK10 RCBO, 2-pole, 10 A, B-curve, 6","metaDescription":"Siemens SENTRON 5SV9316-0PK10 RCD-operated circuit breaker, 2-pole 1P+N, 10 A rated current, B tripping characteristic, 6 kA breaking capacity (EN 60898 / IEC 60947-2). Active prod","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","at 30 Cel":"10 A","at 40 Cel":"9.4 A","at 45 Cel":"9.1 A","at 50 Cel":"8.7 A","at 55 Cel":"8.4 A","Silicon-Free":"Yes","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Degree of pollution":"2","Operating frequency":"50/60 Hz","Product designation":"RCD-operated circuit breaker","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","at AC / rated value":"230/240 V","Overvoltage category":"III","Design of the product":"Instantaneous","Energy limiting class":"3","Number of width units":"1","Type of fault current":"AC","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SV9","Tripping characteristic class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"from below","Number of poles / with protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product feature / Touch protection":"Yes","Supply voltage frequency / rated value":"50 Hz","Operating current / at AC / rated value":"10 A","Tripping residual current / rated value":"30 mA","Influence of the surrounding temperature":"Max. 95% humidity","Surge current resistance / at (8/20) μs":"1 kA","Product function / neutral conductor switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695064&mlfb=5SV9316-0PK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-0PK10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV9316-0PK10?","answer":"6 kA per EN 60898 and IEC 60947-2, sufficient for most residential and light commercial sub-distribution boards."},{"question":"Will 5SV9316-0PK10 drop into a panel that was specified around 5SV9316-1NK06 without rewiring?","answer":"Both are 1-pole+N RCBOs in the same 18 mm width, so mechanical fit is the same. However, 5SV9316-1NK06 carries a different current rating and tripping curve; verify the circuit's load and selectivity requirements before swapping."},{"question":"Where can I buy 5SV9316-0PK10 and how is it quoted?","answer":"Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-0PK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-0PK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}