{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-1NK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-1NK06","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-1NK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-1NK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SV9316-1NK06, 1P+N, 6 A, C characteristic, 30 mA residual current, 6 kA breaking capacity.","salesMarkdown":"It protects a single final circuit against both overload/short-circuit (C-curve magnetic trip) and earth leakage (30 mA AC type). The 1P+N configuration switches the line conductor only; the neutral is switched through but not protected. The 18 mm width (1 modular unit) means it occupies a single DIN-rail slot — important for panel fill factor when packing multiple RCBOs into a consumer unit or sub-distribution board. The 30 mA residual current trip protects against direct-contact earth faults in standard domestic and commercial installations. Temperature derating is significant: at 40 °C the continuous rating drops to 5.64 A, at 50 °C to 5.22 A. If the distribution board runs warm — common in summer or high-density enclosures — size the upstream circuit accordingly. The 5SV9316-1NK06 is an instantaneous (non-time-delayed) RCBO. For selective coordination with downstream RCDs, a time-delayed type (S-curve) would be needed upstream — this unit trips without intentional delay.","metaTitle":"Siemens 5SV9316-1NK06 SENTRON RCBO, 6A C-curve, 30mA, 1P+N","metaDescription":"Siemens 5SV9316-1NK06 SENTRON RCBO, 6A rated, C-curve, 30mA residual current, 6kA breaking capacity. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9316-1NK06","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 1P+N, Type AC, 30 mA, C-Char, In: 6 A, Un AC: 240 V, compact","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"6 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Weight With Packaging":"135 g","at 30 °C rated value":"6 A","at 40 °C rated value":"5.64 A","at 45 °C rated value":"5.46 A","at 50 °C rated value":"5.22 A","at 55 °C rated value":"5.04 A","Energy Limitation Class":"3","according to EN 61346-2":"F","according to IEC 81346-2":"F","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"1.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=765317&mlfb=5SV9316-1NK06"},"ai":{"faq":[{"question":"What is the closest functional second-source to 5SV9316-1NK06?","answer":"The closest functional peer within the SENTRON family is the 5SU9354-7KK16, which shares the same 1P+N, 6 A, C-curve, 30 mA specification. The 5SV9316-1NK06 is an instantaneous RCBO; verify that the peer's time-delay characteristic (if any) matches your selectivity scheme before substituting."},{"question":"Will 5SV9316-1NK06 drop into a panel specified around 5SU9354-7KK16 without rewiring?","answer":"Yes — both are 18 mm wide, 1-module-width RCBOs with the same pole configuration (1P+N) and top/bottom feed. The footprint and DIN-rail clip are identical. No rewiring is needed for the physical swap, but confirm the peer's time-delay characteristic if selectivity is critical."},{"question":"Where can I buy 5SV9316-1NK06 and how is it quoted?","answer":"This part is sourced through independent industrial-automation distribution. Submit an RFQ for current pricing and availability — stock levels and lead time are confirmed at quote time, not published here."},{"question":"What compliance documentation does Siemens provide for 5SV9316-1NK06?","answer":"The part carries halogen-free and silicon-free declarations. Standard documentation includes the manufacturer's declaration of conformity to EN 60898 and IEC 60947-2, plus RoHS and REACH compliance statements available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-1NK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-1NK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}