{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-1NK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-1NK16","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-1NK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-1NK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-1NK16, 2-pole RCBO, 16 A rated, 30 mA residual current, C tripping characteristic, 6 kA breaking capacity (EN 60898 / IEC 60947-2).","salesMarkdown":"The 16 A rated current at 30 °C and C tripping characteristic mean it handles moderate inrush loads — typical for mixed lighting and small motor circuits in commercial panels — while the 30 mA residual threshold protects against direct-contact shock hazards. For circuits with variable-speed drives, UPS systems, or LED drivers that can generate non-sinusoidal leakage, a type A or type B RCD would be required. The 16 A rating holds at 30 °C ambient; at 40 °C it derates to 15.2 A, at 45 °C to 14.72 A, at 50 °C to 14.24 A, and at 55 °C to 13.76 A. If the panel internal temperature runs above 30 °C — common in crowded enclosures — size the upstream protection and load accordingly. ## Regulatory and compliance notes Rated insulation voltage is 264 V, surge voltage resistance is 4 kV, and the energy limitation class is 3. The product designation per EN 61346-2 and IEC 81346-2 is letter F (protective device).","metaTitle":"Siemens 5SV9316-1NK16 SENTRON RCBO, 16A, 30mA, C-curve, 2-po","metaDescription":"Siemens 5SV9316-1NK16 SENTRON RCBO, 16 A rated, 30 mA residual, C characteristic, 2-pole, 6 kA breaking capacity. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9316-1NK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 1P+N, Type AC, 30 mA, C-Char, In: 16 A, Un AC: 240 V, compact","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Energy Limitation Class":"3","Weight / With Packaging":"135 g","according to EN 61346-2":"F","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.72 A","at 50 °C / rated value":"14.24 A","at 55 °C / rated value":"13.76 A","according to IEC 81346-2":"F","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","according to EN 60898 / rated value":"6 kA","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","according to IEC 60947-2 / rated value":"6 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=764922&mlfb=5SV9316-1NK16"},"ai":{"faq":[{"question":"What are the key ratings of the 5SV9316-1NK16?","answer":"16 A rated current at 30 °C, 30 mA residual fault current, C tripping characteristic, 6 kA breaking capacity per EN 60898 and IEC 60947-2, 2 poles, 264 V insulation voltage, and 4 kV surge voltage resistance."},{"question":"Where can I buy the 5SV9316-1NK16 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What is the physical size of the 5SV9316-1NK16?","answer":"Width is 18 mm (1 modular width unit), depth is 77 mm, installation depth is 70 mm, and height is 90 mm."},{"question":"Does the 5SV9316-1NK16 drop into a panel specified around a 5SL6120-7?","answer":"Both are 2-pole, 18 mm wide DIN-rail RCBOs from the SENTRON family, so the physical footprint is the same. However, the 5SL6120-7 is a different order code with potentially different ratings or internal construction — verify the specific electrical parameters against your BOM before substituting."},{"question":"What compliance documentation is available for the 5SV9316-1NK16?","answer":"The device carries IEC 60947-2 and EN 60898 ratings, is halogen-free and silicon-free, and is designed to overvoltage category III and pollution degree 2. Standard Siemens declarations of conformity and CE marking apply; specific RoHS/REACH declarations are available from the manufacturer on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-1NK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-1NK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}