{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-1NK25","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-1NK25","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-1NK25","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-1NK25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 25A rated operational current, 30mA rated residual fault current, Type AC, C tripping characteristic, 1P+N, 6kA breaking capacity per EN 60898 and IEC 60947-2, 18mm modular width.","salesMarkdown":"The Siemens SENTRON 5SV9316-1NK25 is a combined residual-current-operated circuit breaker (RCBO) that packs overcurrent and earth-fault protection into a single 18 mm module. It is rated 25 A operational current with a 30 mA residual fault trip threshold, Type AC (sinusoidal AC residual currents only), C-curve magnetic release, 1P+N (switched neutral), and a 6 kA breaking capacity certified to both EN 60898 and IEC 60947-2. At 25 A and C-curve, this RCBO is sized for general-purpose final circuits with moderate inrush — lighting, socket outlets, small appliances — not motor or transformer loads where a D-curve would be needed. The 6 kA breaking capacity (Icn = 6 kA per EN 60898, Icu = 6 kA per IEC 60947-2) is adequate for most domestic and light commercial installations where the prospective short-circuit current at the point of installation is below 6 kA. In industrial panels with higher fault levels, a current-limiting upstream MCCB or fuse would be required for coordination. The 18 mm width (1 modular unit) and 77 mm depth let it fit standard DIN-rail enclosures without crowding adjacent devices. Mounting position is unrestricted. The IP20 rating applies only when the distribution board is installed with connected conductors — this is a panel-internal device, not a field-mounted unit. The product carries an overvoltage category III rating (fixed installation, not plug-connected equipment) and pollution degree 2 (non-conductive dust, occasional condensation). These are standard for residential and commercial panelboard components.","metaTitle":"Siemens SENTRON 5SV9316-1NK25 RCBO, 25A, 30mA, Type AC, C-cu","metaDescription":"Siemens SENTRON 5SV9316-1NK25 RCBO, 25A rated current, 30mA residual current, Type AC, C-curve, 6kA breaking capacity, 1P+N, 18mm wide. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9316-1NK25","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 1P+N, Type AC, 30 mA, C-Char, In: 25 A, Un AC: 240 V, compact","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"230/240 V","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"135 g","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","operational current / at AC / rated value":"25 A","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=764924&mlfb=5SV9316-1NK25"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV9316-1NK25?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels; no real-time figures are published here."},{"question":"Will the 5SV9316-1NK25 drop into a panel specified around the 5SL6016-7KL without rewiring?","answer":"Both are 1-module-wide (18 mm) DIN-rail devices with similar pole configurations, but the 5SL6016-7KL is a standard MCB without residual current protection, while the 5SV9316-1NK25 is an RCBO that requires a neutral connection for the electronic trip circuit. Mechanical fit is the same; electrical wiring differs because the RCBO needs the neutral passed through the device."},{"question":"What compliance documentation does Siemens provide for the 5SV9316-1NK25?","answer":"The product is certified to EN 60898 and IEC 60947-2 for breaking capacity, carries overvoltage category III and pollution degree 2 ratings, and is halogen-free and silicon-free. Standard Siemens declarations of conformity (CE, UKCA) and material compliance (RoHS, REACH) are available through the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-1NK25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-1NK25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}