{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-1NK32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-1NK32","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-1NK32","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-1NK32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-1NK32, 2-pole RCBO, C-curve 32 A, 30 mA AC type residual current, 6 kA breaking capacity per EN 60898 / IEC 60947-2.","salesMarkdown":"Residual current sensitivity is 30 mA, AC type — the standard for personnel protection in residential and commercial final circuits. Not for high-inrush loads (D-curve territory) or purely resistive circuits (B-curve). Depth is 77 mm with 70 mm installation depth; the top or bottom supply position is flexible for panel layout. Temperature derating applies: 32 A at 30 °C ambient, 30.4 A at 40 °C, 28.8 A at 50 °C. Mounting position any, but derate per the published curve when packing multiple units in a closed enclosure. Touch protection is integral. Compliance per IEC 81346-2 and DIN EN 61346-2 function designation F.","metaTitle":"Siemens 5SV9316-1NK32 SENTRON RCBO, 2P, C-32A, 30mA, 6kA","metaDescription":"Siemens 5SV9316-1NK32 SENTRON RCBO, 2-pole, C-curve 32A, 30mA residual current, 6kA breaking capacity. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9316-1NK32","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 1P+N, Type AC, 30 mA, C-Char, In: 32 A, Un AC: 240 V, compact","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"32 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"135 g","at 30 °C / rated value":"32 A","at 40 °C / rated value":"30.4 A","at 45 °C / rated value":"29.44 A","at 50 °C / rated value":"28.8 A","at 55 °C / rated value":"27.84 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=764925&mlfb=5SV9316-1NK32"},"ai":{"faq":[{"question":"Where can I buy 5SV9316-1NK32?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published on this listing."},{"question":"What is the breaking capacity of 5SV9316-1NK32?","answer":"6 kA per EN 60898 and IEC 60947-2 — sufficient for sub-distribution boards with a 6 kA prospective fault level."},{"question":"What is the residual current sensitivity and type?","answer":"30 mA, AC type — the standard for personnel protection in final circuits against sinusoidal AC earth faults."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-1NK32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-1NK32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}