{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-1PK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-1PK10","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-1PK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-1PK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-1PK10, RCD-operated circuit breaker (RCBO), Type AC, 1P+N, 10 A rated current, 6 kA breaking capacity, C characteristic, 230/240 V AC.","salesMarkdown":"The Siemens 5SV9316-1PK10 is a SENTRON RCBO — a combined RCD and MCB in one 18 mm wide unit (1 width unit). It's a 1P+N design: one protected pole switched, neutral switched but not protected. ## Ratings that matter for the panel At 40 °C it's 9.4 A, at 45 °C it's 9.1 A, at 50 °C it's 8.7 A, and at 55 °C it's 8.4 A. If the distribution board runs hot, factor that derating into the circuit design. The test button needs at least 195 V to operate correctly. The IP20 rating applies only when the distribution board is installed with conductors connected.","metaTitle":"Siemens 5SV9316-1PK10 SENTRON RCBO, 10 A, 6 kA, Type AC","metaDescription":"Siemens SENTRON 5SV9316-1PK10 RCBO. 10 A rated, 6 kA breaking capacity (EN 60898), Type AC, 1P+N, 230/240 V. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","at 30 Cel":"10 A","at 40 Cel":"9.4 A","at 45 Cel":"9.1 A","at 50 Cel":"8.7 A","at 55 Cel":"8.4 A","Silicon-Free":"Yes","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Degree of pollution":"2","Operating frequency":"50/60 Hz","Product designation":"RCD-operated circuit breaker","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","at AC / rated value":"230/240 V","Overvoltage category":"III","Design of the product":"Instantaneous","Energy limiting class":"3","Number of width units":"1","Type of fault current":"AC","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SV9","Tripping characteristic class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"from below","Number of poles / with protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product feature / Touch protection":"Yes","Supply voltage frequency / rated value":"50 Hz","Operating current / at AC / rated value":"10 A","Tripping residual current / rated value":"30 mA","Influence of the surrounding temperature":"Max. 95% humidity","Surge current resistance / at (8/20) μs":"1 kA","Product function / neutral conductor switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695070&mlfb=5SV9316-1PK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-1PK10/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 5SV9316-1PK10?","answer":"Current pricing and availability are confirmed at quote time. Submit an RFQ through the storefront; we source through independent distribution and quote to order."},{"question":"What is the 5SV9316-1PK10's depth and width?","answer":"The depth is 77 mm, the width is 18 mm (1 width unit), and the height is 90 mm. Installation depth into the panel is 70 mm."},{"question":"What compliance documentation does this RCBO carry?","answer":"The 5SV9316-1PK10 is rated per EN 60898 and IEC 60947-2 for a 6 kA breaking capacity. It carries overvoltage category III and pollution degree 2 ratings. The silicon-free construction and touch protection are documented features."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-1PK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-1PK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}