{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-1PK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-1PK16","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-1PK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-1PK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-1PK16 RCBO, 2-pole (1P+N), 16 A rated, 30 mA residual current, Type AC, tripping characteristic C, 6 kA breaking capacity, 1 MW modular width.","salesMarkdown":"The Siemens 5SV9316-1PK16 is a 2-pole (1P+N) SENTRON RCD-operated circuit breaker — an RCBO that combines overcurrent protection and residual current protection in a single 18 mm wide module. The C-curve tripping characteristic means it holds 5–10× In for short-duration inrush, making it a standard fit for general-purpose circuits feeding lighting, socket outlets, and small motor loads in commercial and industrial distribution boards. One modular width unit (18 mm) snaps onto DIN rail. Depth is 77 mm, installation depth 70 mm — the extra 7 mm is the front projection of the toggle and test button. Mounting position is unrestricted; supply feeds from below per standard practice. IP20 applies once the distribution board is installed and conductors are connected — the RCBO itself is not sealed for wet environments. Touch protection is built in on the line-side terminals. ## Thermal derating and environmental limits At 40 °C it derates to 15.2 A, at 45 °C to 14.72 A, at 50 °C to 14.24 A, and at 55 °C to 13.76 A.","metaTitle":"Siemens 5SV9316-1PK16 SENTRON RCBO, 2-pole, 16A, 30mA, Type","metaDescription":"Siemens 5SV9316-1PK16 SENTRON RCBO, 2-pole 1P+N, 16A rated, 30mA residual current, Type AC, C-curve, 6kA breaking capacity. Active production, available to order. Quoted on request","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9316-1PK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 1P+N, Type AC, 30 mA, C-Char, In: 16 A, Un AC: 240 V, pigtail 600 mm","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"155 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.72 A","at 50 °C / rated value":"14.24 A","at 55 °C / rated value":"13.76 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"from below","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695071&mlfb=5SV9316-1PK16"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV9316-1PK16?","answer":"6 kA per both EN 60898 and IEC 60947-2, which covers standard residential and light commercial fault levels."},{"question":"What is the width and modular width of this RCBO?","answer":"18 mm wide, which is 1 modular width unit (MW) on standard DIN rail."},{"question":"Will 5SV9316-1PK16 drop into a panel specified around 5SL6120-7 without rewiring?","answer":"Both are 1 MW wide, DIN-rail mount, and 1P+N — so the mechanical fit is the same. But 5SL6120-7 is a plain MCB (no residual current protection), while this is an RCBO with a 30 mA trip. If the panel was wired for a separate RCD plus MCB, swapping to this changes the protection scheme and may require re-termination of the neutral."},{"question":"Where can I buy 5SV9316-1PK16?","answer":"Sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-1PK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-1PK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}