{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-6FM20","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-6FM20","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-6FM20","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6FM20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 5SV9316-6FM20, RCBO, Icn 6 kA, 1P+N, type A, 30 mA, B-Char, In 20 A, Un AC 240 V, compact, reduced i²t.","salesMarkdown":"Type A RCD detection handles pulsating DC fault currents up to 6 mA superimposed on AC — covers electronics, rectifiers, and single-phase drives that a Type AC device might miss. The 30 mA sensitivity is the standard for personal protection against indirect contact (IEC 60364). B-curve tripping (3–5 × In) means the magnetic release operates between 60 A and 100 A, matching resistive or lightly inductive loads like lighting, socket outlets, or small appliances without nuisance trips from inrush. Rated at 20 A, 240 V AC, single-pole switched plus neutral. The compact 1-module width (18 mm per DIN rail pitch) saves enclosure space compared to separate RCD + MCB pairs — a consideration when filling a TP+N board with multiple final circuits. Wire termination accepts up to 25 mm² copper conductor; torque setting per the terminal marking. The reduced i²t let-through energy aids downstream selectivity with upstream MCCBs or fuses — a coordination point for the panel designer reviewing the fault discrimination study.","metaTitle":"Siemens 5SV9316-6FM20 RCBO, 6 kA, 1P+N, Type A, 30 mA, B-Cha","metaDescription":"Siemens 5SV9316-6FM20 RCBO, 6 kA breaking capacity, 1P+N, Type A RCD 30 mA, B-curve 20 A, 240 V AC. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1399064&mlfb=5SV9316-6FM20","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6FM20/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the 5SV9316-6FM20?","answer":"RCBO with 6 kA breaking capacity, 1P+N, Type A RCD at 30 mA, B-curve overcurrent protection at 20 A, rated 240 V AC. Compact reduced i²t design."},{"question":"Where can I buy the 5SV9316-6FM20?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-6FM20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-6FM20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}