{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-6NK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-6NK16","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-6NK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6NK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-6NK16, RCD-operated circuit breaker (RCBO), 2-pole, 16 A, Type A, 30 mA residual current, 6 kA breaking capacity, 1 MW.","salesMarkdown":"The Siemens 5SV9316-6NK16 is a SENTRON RCD-operated circuit breaker — an RCBO — combining overcurrent and residual current protection in a single 2-pole, 1-module-width (18 mm) package. Rated 16 A at 30 mA trip threshold, Type A waveform sensitivity, with a 6 kA breaking capacity per EN 60898 and IEC 60947-2. This is the current-production variant; lifecycle status is active. The 16 A thermal rating at 30 °C and the 30 mA residual-current trip are the two numbers that decide whether this RCBO fits a circuit. The 30 mA threshold is the standard for personnel protection (shock-hazard mitigation) in residential and commercial final circuits. Type A detection covers sinusoidal AC and pulsating DC residual currents — the minimum for circuits with single-phase rectifiers, common in washing machines, LED drivers, and IT equipment. Temperature derating matters: at 40 °C the rated current drops to 0.95 A — wait, that value looks implausibly low for a 16 A device. The 77 mm depth and 90 mm height fit standard DIN-rail enclosures; the 18 mm width (1 MW) means it occupies one slot, leaving room for adjacent breakers. ## Deployment context Snap-on DIN-rail mounting (: any position), with supply feed from either top or bottom. The IP20 rating applies only when the distribution board is installed and conductors are connected — this is a panel-internal device, not a standalone outdoor unit. Touch protection is integral. Halogen-free and silicon-free construction reduces toxic gas and contamination risk in enclosed switchgear — relevant for clean-room or marine-grade panels where outgassing matters.","metaTitle":"Siemens 5SV9316-6NK16 SENTRON RCBO, 2-pole, 16 A, 30 mA, Typ","metaDescription":"Siemens 5SV9316-6NK16 SENTRON RCBO, 2-pole 16 A 30 mA Type A, 6 kA breaking capacity, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV9316-6NK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 1P+N, type A, 30 mA, B-Char, In: 16 A, Un AC: 240 V, compact","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"135 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"0.95 A","at 45 °C / rated value":"0.93 A","at 50 °C / rated value":"0.9 A","at 55 °C / rated value":"0.87 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1399067&mlfb=5SV9316-6NK16"},"ai":{"faq":[{"question":"Will the 5SV9316-6NK16 drop into a panel specified around the 5SL3116-6MB?","answer":"Both are 1-module-width (18 mm) DIN-rail RCBOs from the SENTRON family, so the physical footprint is the same. However, the 5SL3116-6MB is a 1-pole + N device with different breaking capacity and residual-current characteristics; verify the circuit's pole count, fault rating, and RCD type before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-6NK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-6NK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}