{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-6PK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-6PK16","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-6PK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-6PK16, RCD-operated circuit breaker, 1P+N, 16 A rated, 30 mA residual current, Type A, B characteristic, 6 kA breaking capacity.","salesMarkdown":"It protects a single-phase (1P+N) circuit against overload, short-circuit, and earth faults, with a 30 mA residual-current trip threshold and a B tripping characteristic for resistive or light inductive loads. Rated 16 A at 30 °C, it derates to 15.2 A at 40 °C and 13.76 A at 55 °C — the thermal curve matters if the distribution board runs warm. The Type A residual-current detection handles pulsating DC faults — common with electronics, rectifiers, and variable-speed drives — not just sinusoidal AC. That makes it a better fit than a basic Type AC for modern loads. At 18 mm wide (1 MW), it takes minimal panel space. Depth is 77 mm, installation depth 70 mm — check the gland plate clearance if the enclosure is shallow. Supply connects from below per the design. Silicon-free construction matters for environments where silicone outgassing can contaminate contacts or optics — automotive paint shops or certain clean-room lines, for instance.","metaTitle":"Siemens 5SV9316-6PK16 SENTRON RCD-MCB, 16A, 30mA, Type A, B","metaDescription":"Siemens 5SV9316-6PK16 SENTRON RCD-operated circuit breaker, 1P+N, 16A rated, 30mA residual current, Type A, B curve, 6kA breaking capacity. Current lifecycle stage. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"155 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.72 A","at 50 °C / rated value":"14.24 A","at 55 °C / rated value":"13.76 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"from below","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695077&mlfb=5SV9316-6PK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK16/alternatives.json"},"ai":{"faq":[{"question":"What is the 5SV9316-6PK16's depth?","answer":"The depth is 77 mm, with an installation depth of 70 mm."},{"question":"What is the 5SV9316-6PK16's width?","answer":"The width is 18 mm, which is one modular width unit (1 MW) on a standard DIN rail."},{"question":"Where can I buy the 5SV9316-6PK16?","answer":"It is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quotation."},{"question":"Will the 5SV9316-6PK16 drop into a panel specified around the 5SL3116-6MB?","answer":"The 5SL3116-6MB is a standard MCB (no RCD), while the 5SV9316-6PK16 is an RCBO with the same 1-module width and DIN-rail footprint. It will fit the same rail and panel cutout, but the wiring differs because the RCBO needs the neutral connection through the device. No rewiring of the busbar is required if the neutral is already routed through the RCBO position."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-6PK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-6PK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}