{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-6PK32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-6PK32","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-6PK32","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-6PK32, RCD-operated circuit breaker (RCBO), 2-pole 1P+N, Type A, 30 mA residual current, B-curve, 32 A rated, 6 kA breaking capacity.","salesMarkdown":"The 5SV9316-6PK32: The 30 mA residual-current trip (Type A) means it catches both sinusoidal AC faults and pulsating DC faults up to 6 mA smooth DC — the minimum required by IEC 60364 for socket-outlet circuits in most jurisdictions. The 6 kA SCCR at 230/400 V per EN 60898 and IEC 60947-2 is adequate for most TN and TT systems; if your service entrance has a higher prospective fault current, you'll need an upstream current-limiting MCB or fuse to back up this device. Temperature derating is built into the spec: at 40 °C ambient the continuous current drops to 30.4 A, at 50 °C to 28.8 A. ## Integration notes The supply feeds from below per the manufacturer's marking. The touch-protection feature (finger-safe terminals) is built in, so no separate terminal covers are needed for the front face. Silicon-free construction matters for applications where outgassing could contaminate sensitive contacts or optics.","metaTitle":"Siemens 5SV9316-6PK32 SENTRON RCBO, Type A, 32 A, 30 mA, B-C","metaDescription":"Siemens 5SV9316-6PK32 SENTRON RCD-operated circuit breaker, 2-pole 1P+N, 32 A, 30 mA residual current, Type A, B-curve, 6 kA. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"32 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"155 g","at 30 °C / rated value":"32 A","at 40 °C / rated value":"30.4 A","at 45 °C / rated value":"29.44 A","at 50 °C / rated value":"28.8 A","at 55 °C / rated value":"27.84 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"from below","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695079&mlfb=5SV9316-6PK32","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK32/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV9316-6PK32 and how do I get a price?","answer":"The 5SV9316-6PK32 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 5SV9316-6PK32's listed depth (77 mm) on this component line?","answer":"The 5SV9316-6PK32 has a depth of 77 mm, with an installation depth of 70 mm behind the DIN rail. The width is 18 mm (1 modular width unit), and height is 90 mm."},{"question":"Will 5SV9316-6PK32 drop into a panel that was specified around 5SL6550-7BB without rewiring?","answer":"The 5SV9316-6PK32 is a different product class — it's an RCBO (RCD + MCB combined) while the 5SL6550-7BB is a standalone MCB. The 5SV9316-6PK32 requires both line and neutral connections (1P+N), whereas a standard MCB only switches the line. It will not drop in as a direct mechanical or wiring replacement without adding the neutral conductor and verifying the residual-current protection is appropriate for the circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-6PK32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-6PK32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}