{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-6PK32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-6PK32","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-6PK32","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-6PK32, RCD-operated circuit breaker (RCBO), 2-pole 1P+N, Type A, 30 mA residual current, B-curve, 32 A rated, 6 kA breaking capacity.","salesMarkdown":"The 5SV9316-6PK32: The 30 mA residual-current trip (Type A) means it catches both sinusoidal AC faults and pulsating DC faults up to 6 mA smooth DC — the minimum required by IEC 60364 for socket-outlet circuits in most jurisdictions. The 6 kA SCCR at 230/400 V per EN 60898 and IEC 60947-2 is adequate for most TN and TT systems; if your service entrance has a higher prospective fault current, you'll need an upstream current-limiting MCB or fuse to back up this device. Temperature derating is built into the spec: at 40 °C ambient the continuous current drops to 30.4 A, at 50 °C to 28.8 A. ## Integration notes The supply feeds from below per the manufacturer's marking. The touch-protection feature (finger-safe terminals) is built in, so no separate terminal covers are needed for the front face. Silicon-free construction matters for applications where outgassing could contaminate sensitive contacts or optics.","metaTitle":"Siemens 5SV9316-6PK32 SENTRON RCBO, Type A, 32 A, 30 mA, B-C","metaDescription":"Siemens 5SV9316-6PK32 SENTRON RCD-operated circuit breaker, 2-pole 1P+N, 32 A, 30 mA residual current, Type A, B-curve, 6 kA. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"18 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695079&mlfb=5SV9316-6PK32","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK32/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-6PK32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-6PK32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}