{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-6PK40","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-6PK40","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-6PK40","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-6PK40, RCD-operated circuit breaker, 2-pole 1P+N, 40 A rated, 30 mA residual current, Type A, 6 kA breaking capacity, tripping characteristic B, instantaneous design.","salesMarkdown":"The Siemens 5SV9316-6PK40 is a SENTRON RCD-operated circuit breaker (RCBO) combining overcurrent protection and residual current detection in a single 2-pole, 1P+N module. It is rated 40 A at 30 °C with a 30 mA residual trip threshold, Type A (pulsating DC and AC sensitive), and a 6 kA breaking capacity per EN 60898 and IEC 60947-2. The silicon-free construction matters for potting or conformal-coating processes in sensitive electronics environments. ## Thermal derating and environmental limits Derate to 38 A at 40 °C, 36.8 A at 45 °C, 36 A at 50 °C, and 34.8 A at 55 °C. Operating ambient range is -40 to 75 °C, with max 95% humidity.","metaTitle":"Siemens 5SV9316-6PK40 SENTRON RCBO, 40A, 30mA, Type A, 6kA","metaDescription":"Siemens 5SV9316-6PK40 SENTRON RCD-operated circuit breaker, 40A rated, 30mA residual current, Type A, 6kA breaking capacity, 2-pole 1P+N, instantaneous design. Active lifecycle, so","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"40 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"155 g","at 30 °C / rated value":"40 A","at 40 °C / rated value":"38 A","at 45 °C / rated value":"36.8 A","at 50 °C / rated value":"36 A","at 55 °C / rated value":"34.8 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"from below","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695080&mlfb=5SV9316-6PK40","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-6PK40/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV9316-6PK40?","answer":"The 5SV9316-6PK40 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the breaking capacity of 5SV9316-6PK40?","answer":"The 5SV9316-6PK40 has a 6 kA breaking capacity rated per both EN 60898 and IEC 60947-2."},{"question":"What residual current type is 5SV9316-6PK40?","answer":"It is Type A, meaning it detects sinusoidal AC residual currents and pulsating DC residual currents up to 30 mA rated fault current."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-6PK40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-6PK40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}