{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-7CN16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-7CN16","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-7CN16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7CN16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-7CN16, RCD-operated circuit breaker, 1P+N, 16 A at 30 °C, Type A, 6 kA, 18 mm wide.","salesMarkdown":"The Siemens 5SV9316-7CN16 is a 1P+N RCD-operated circuit breaker from the SENTRON 5SV9 series — an RCBO that combines overcurrent and residual-current protection in a single 18 mm wide module. The Type A fault-current detection means it catches pulsating DC residual currents from electronics, rectifiers, and variable-speed drives, not just sinusoidal AC faults. At 40 °C it derates to 15.2 A, at 45 °C to 14.72 A, at 50 °C to 14.24 A, and at 55 °C to 13.76 A. If the panel runs warm — say a crowded enclosure near a conveyor drive cabinet — size the branch circuit for the actual ambient, not the 30 °C headline number.","metaTitle":"Siemens 5SV9316-7CN16 RCD Circuit Breaker, 16 A, Type A, 6 k","metaDescription":"Siemens SENTRON 5SV9316-7CN16 RCD-operated circuit breaker, 16 A at 30 °C, Type A, 6 kA breaking capacity, 1P+N, 18 mm wide. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","at 30 Cel":"16 A","at 40 Cel":"15.2 A","at 45 Cel":"14.72 A","at 50 Cel":"14.24 A","at 55 Cel":"13.76 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Degree of pollution":"2","Operating frequency":"50/60 Hz","Product designation":"RCD-operated circuit breaker","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","at AC / rated value":"230/240 V","Overvoltage category":"III","Design of the product":"Instantaneous","Energy limiting class":"3","Number of width units":"1","Type of fault current":"A","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SV9","Tripping characteristic class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"Either top or bottom","Number of poles / with protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product feature / Touch protection":"Yes","Supply voltage frequency / rated value":"50 Hz","Operating current / at AC / rated value":"16 A","Tripping residual current / rated value":"30 mA","Influence of the surrounding temperature":"Max. 95% humidity","Surge current resistance / at (8/20) μs":"1 kA","Product function / neutral conductor switching":"Yes","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=765471&mlfb=5SV9316-7CN16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7CN16/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV9316-7CN16?","answer":"It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the difference between 5SV9316-7CN16 and 5SL6550-7BB?","answer":"The 5SL6550-7BB is a standard MCB without residual-current protection — it only provides overcurrent and short-circuit protection. The 5SV9316-7CN16 is an RCBO that adds Type A ground-fault detection in the same 18 mm footprint. If the panel needs RCD protection per local code, the 5SV9316-7CN16 replaces both a separate MCB and RCCB in one unit."},{"question":"What compliance documentation is available for 5SV9316-7CN16?","answer":"The part carries a halogen-free and silicon-free construction. It is designed to meet EN 60898 and IEC 60947-2 for breaking capacity, and it is rated for overvoltage category III and pollution degree 2. Specific RoHS/REACH declarations and the manufacturer's declaration of conformity are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-7CN16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-7CN16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}