{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-7NK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-7NK06","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-7NK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7NK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCD-operated circuit breaker, 1P+N, 6 A, C characteristic, 30 mA, Type A, 6 kA, 1 MW.","salesMarkdown":"The Siemens SENTRON 5SV9316-7NK06 is an RCD-operated circuit breaker — an RCBO — combining overcurrent protection and residual current detection in a single 1 MW (18 mm) module. It's rated 6 A with a C tripping characteristic, 30 mA residual sensitivity, Type A (pulsating DC and AC fault currents), and a 6 kA breaking capacity per EN 60898 and IEC 60947-2. The 30 mA residual trip threshold covers personnel protection (hand-to-hand or hand-to-ground fault path) per IEC 60364. ## Temperature derating — the number that actually governs your load At 40 °C it derates to 5.64 A; at 45 °C to 5.46 A; at 50 °C to 5.22 A; at 55 °C to 5.04 A. If this RCBO lives in a crowded enclosure or near a heat source, size the upstream load against the derated figure, not the 30 °C headline. A 5.5 A continuous draw at 50 °C is fine; a full 6 A at that temperature will nuisance-trip on thermal overload. ## Panel fit and installation constraints Snaps onto DIN rail (35 mm EN 60715) in any mounting position. The 18 mm width (1 MW) means it occupies one modular slot — tight for a 1P+N RCBO with both overcurrent and RCD in one unit. Supply can enter from top or bottom; the design is instantaneous (no intentional time delay on the RCD element), so it's not suitable for selectivity with downstream Type G/S delayed RCDs — coordinate on time grading if used in a multi-level RCD scheme. IP20 rating applies only when installed in a distribution board with conductors connected — the terminals are finger-safe but the module itself is not sealed against dust ingress. Halogen-free and silicon-free construction (no silicone outgassing issues in clean environments or near sensitive contacts). Insulation voltage rated 264 V; surge voltage resistance 4 000 V; surge current withstand 1 kA (8/20 μs waveform). The manufacturer provides EN/IEC declaration of conformity and CE marking; RoHS and REACH compliance documentation is standard with the SENTRON series.","metaTitle":"Siemens 5SV9316-7NK06 SENTRON RCBO, 6A, Type A, 30mA, 6kA","metaDescription":"Siemens SENTRON 5SV9316-7NK06 RCBO (RCD-operated circuit breaker). 6A rated, Type A, 30mA residual current, 6kA breaking capacity. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"6 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Weight With Packaging":"135 g","at 30 °C rated value":"6 A","at 40 °C rated value":"5.64 A","at 45 °C rated value":"5.46 A","at 50 °C rated value":"5.22 A","at 55 °C rated value":"5.04 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"1.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=764926&mlfb=5SV9316-7NK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7NK06/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV9316-7NK06 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"Will 5SV9316-7NK06 drop into a panel specified for 5SV9316-1NK06?","answer":"Both are 1 MW, 1P+N SENTRON RCBOs with the same 6 A / C-curve / 30 mA / Type A / 6 kA ratings. The -7NK06 variant carries the halogen-free and silicon-free material compliance; the -1NK06 does not. Mechanically they are interchangeable on the same DIN-rail footprint and wiring scheme."},{"question":"What compliance documentation does Siemens provide for 5SV9316-7NK06?","answer":"Standard SENTRON documentation includes EN/IEC declaration of conformity, CE marking, and RoHS/REACH material compliance. The part is halogen-free and silicon-free per the spec sheet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-7NK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-7NK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}