{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-7NK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-7NK10","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-7NK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7NK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SV9316-7NK10, 1P+N, 10 A, C-curve, 6 kA, 230/240 V AC, 18 mm wide, instantaneous.","salesMarkdown":"The 1P+N pole configuration switches the line conductor and disconnects the neutral, fitting standard single-phase residential and light-commercial distribution boards. The 10 A rating at 30 °C is the headline number, but the derating curve matters more in a warm panel: at 40 °C it carries 9.4 A, at 45 °C it drops to 9.1 A, and at 55 °C it's down to 8.4 A. If your ambient inside the enclosure runs above 40 °C, size the branch circuit load against the derated value, not the 30 °C figure. Rated insulation voltage (Ui) is 264 V, and it's rated for 230/240 V AC supply at 50/60 Hz. The surge voltage resistance of 4 kV and surge current withstand of 1 kA at 8/20 µs give it reasonable immunity against switching transients and indirect lightning strikes on the mains. The supply can enter from either the top or bottom, which simplifies busbar routing and panel layout. Mounting position is unrestricted — it can be installed horizontally or vertically without derating. IP20 protection applies only when the distribution board is installed and conductors are connected — this is normal for an enclosed panel component.","metaTitle":"Siemens 5SV9316-7NK10 SENTRON RCBO, 10 A C-curve, 6 kA, 1P+N","metaDescription":"Siemens 5SV9316-7NK10 SENTRON RCBO, 10 A rated, C-curve, 6 kA breaking capacity per EN 60898/IEC 60947-2, 1P+N, 18 mm wide. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"135 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.4 A","at 45 °C rated value":"9.1 A","at 50 °C rated value":"8.7 A","at 55 °C rated value":"8.4 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"1.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=764927&mlfb=5SV9316-7NK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7NK10/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV9316-7NK10?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is the closest functional alternative to 5SV9316-7NK10?","answer":"The 5SY4116-7CV is a similar Siemens RCBO but with a B-curve characteristic (magnetic trip 3–5× In) versus the C-curve on this part. For motor or lighting loads with moderate inrush, the C-curve is the better choice; the B-curve suits purely resistive or electronic loads where faster magnetic trip is acceptable."},{"question":"Will 5SV9316-7NK10 drop into a panel specified around 5SY4116-7CV without rewiring?","answer":"Both are 1P+N, 18 mm wide, DIN-rail mount RCBOs with the same terminal layout and supply flexibility (top or bottom feed). The physical swap is straightforward — no busbar or wiring changes needed. The only difference is the tripping curve, so verify the load's inrush characteristic before substituting."},{"question":"What compliance documentation does Siemens provide for 5SV9316-7NK10?","answer":"Standard documentation includes the datasheet, CE declaration of conformity, and manufacturer declarations for RoHS and REACH compliance. The part carries ratings per EN 60898 and IEC 60947-2, which are harmonized European standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-7NK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-7NK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}