{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-7NK32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-7NK32","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-7NK32","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7NK32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-7NK32, RCBO, 1P+N, 32 A, 30 mA, Type A, C-curve, 6 kA, 1 MW.","salesMarkdown":"The Siemens 5SV9316-7NK32 is a SENTRON RCBO — an RCD-operated circuit breaker that combines overcurrent and residual current protection in a single 18 mm wide module. The 32 A rating is at 30 °C ambient; at 40 °C it derates to 30.4 A, and at 50 °C to 28.8 A. The 30 mA residual current is standard for personnel protection (shock risk) in most IEC-based installations. Type A means it catches sinusoidal AC faults and pulsating DC faults up to 6 mA smooth DC superimposed — needed on circuits with single-phase rectifiers, VFDs, or switching power supplies. ## Panel integration At 18 mm (1 MW) wide, it fits a standard modular enclosure slot. Depth is 77 mm, installation depth 70 mm, so it clears a 90 mm deep enclosure with a few mm to spare. IP20 rating applies once the distribution board is installed with conductors connected — treat it as protected inside the enclosure, not for wet locations.","metaTitle":"Siemens 5SV9316-7NK32 SENTRON RCBO, 32A, 30mA, Type A, 6kA","metaDescription":"Siemens 5SV9316-7NK32 SENTRON RCBO, 32A rated, 30mA residual current, Type A, 6kA breaking capacity, C-curve. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"32 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Weight With Packaging":"135 g","at 30 °C rated value":"32 A","at 40 °C rated value":"30.4 A","at 45 °C rated value":"29.44 A","at 50 °C rated value":"28.8 A","at 55 °C rated value":"27.84 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"2.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=764931&mlfb=5SV9316-7NK32","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7NK32/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV9316-7NK32?","answer":"Submit an RFQ through the storefront. We source this part through independent distribution and confirm pricing and availability at quote time — no stock figures or lead-time numbers are published here."},{"question":"What is 5SV9316-7NK32's listed depth?","answer":"The overall depth is 77 mm, with an installation depth of 70 mm."},{"question":"What is 5SV9316-7NK32's listed width?","answer":"Width is 18 mm, which corresponds to 1 modular width unit (1 MW) on a standard DIN-rail panel."},{"question":"Will 5SV9316-7NK32 drop into a panel specified around 5SV9316-1NK06 without rewiring?","answer":"Both are 1 MW wide SENTRON RCBOs with the same pole configuration (1P+N) and similar depth, so the mechanical fit is the same. The electrical substitution depends on whether the ratings match your circuit — compare the rated current, trip curve, and residual current type against your design. This is a form-fit-function check, not a guaranteed drop-in."},{"question":"What compliance documentation does this brand provide for 5SV9316-7NK32?","answer":"The part is halogen-free and silicon-free, which supports environmental compliance requirements. Standard Siemens SENTRON documentation includes the declaration of conformity for the Low Voltage Directive and applicable standards (EN 60898, IEC 60947-2). Specific RoHS/REACH declarations are available from the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-7NK32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-7NK32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}