{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-7PK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-7PK06","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-7PK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7PK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole, 6 A, C-curve, 30 mA residual current, 6 kA breaking capacity per EN 60898 / IEC 60947-2, 1 MW width, IP20.","salesMarkdown":"The C-curve tripping characteristic (6 A rated at 30 °C, derated to 5.64 A at 40 °C and 5.04 A at 55 °C) handles moderate inrush from motorized loads and lighting ballasts; the 30 mA Type A residual-current element catches pulsating DC faults common in modern electronics. ## Panel integration — DIN rail footprint and mounting Width is 18 mm (one modular unit), depth 77 mm, height 90 mm. Installation depth 70 mm — the extra 7 mm is the front toggle and test button. Mounting position any; supply from below. Touch protection is built in. Silicon-free construction matters for potting or conformal-coating environments where silicone outgassing can cause contact failure.","metaTitle":"Siemens SENTRON 5SV9316-7PK06 RCBO, 2P, 6A C, 30mA, 6kA","metaDescription":"Siemens SENTRON 5SV9316-7PK06 RCBO, 2-pole, 6 A, C-curve, 30 mA residual current, 6 kA breaking capacity. Active production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"6 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"155 g","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.64 A","at 45 °C / rated value":"5.46 A","at 50 °C / rated value":"5.22 A","at 55 °C / rated value":"5.04 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"from below","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695081&mlfb=5SV9316-7PK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7PK06/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 5SV9316-7PK06 and how is it quoted for volume purchases?","answer":"Available through independent distribution; sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 5SV9316-7PK06?","answer":"6 kA per EN 60898 and IEC 60947-2 — sufficient for final circuits with prospective fault current under that level."},{"question":"What is the temperature derating curve for this RCBO?","answer":"Rated 6 A at 30 °C, derates to 5.64 A at 40 °C, 5.46 A at 45 °C, 5.22 A at 50 °C, and 5.04 A at 55 °C."},{"question":"What compliance documentation does Siemens provide for 5SV9316-7PK06?","answer":"The product carries EN 60898 and IEC 60947-2 ratings; compliance documentation (declarations of conformity, CE marking) is standard for SENTRON series RCBOs. Specific RoHS, REACH, or UL statements should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-7PK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-7PK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}