{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-7PK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-7PK16","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-7PK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7PK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV9316-7PK16, RCBO, 2-pole, 16 A, 30 mA, Type A, 6 kA, 1 MW, IP20.","salesMarkdown":"The Siemens SENTRON 5SV9316-7PK16 is a 2-pole RCBO — an RCD-operated circuit breaker combining overcurrent and residual current protection in a single 18 mm wide module. It is rated 16 A at 30 °C with a 30 mA residual current trip threshold, Type A (pulsating DC and AC sensitive). The tripping characteristic is Class C, instantaneous design, meaning it trips on short-circuit without intentional delay. Breaking capacity is 6 kA per both EN 60898 and IEC 60947-2, which covers the majority of residential and light commercial distribution board fault levels. Above that, the continuous current must be derated: 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, and 13.76 A at 55 °C. The maximum operating ambient is 75 °C, minimum -40 °C. ## DIN-rail footprint and installation The 5SV9316-7PK16 occupies 1 modular width unit (18 mm) on a standard DIN rail. Depth is 77 mm, height 90 mm, installation depth 70 mm. The supply cord connects from below. Touch protection is provided per the product feature.","metaTitle":"Siemens SENTRON 5SV9316-7PK16 RCBO, 2-pole, 16 A, 30 mA, Typ","metaDescription":"Siemens SENTRON 5SV9316-7PK16 RCBO, 2-pole, 16 A rated, 30 mA residual current, Type A, 6 kA breaking capacity per EN 60898. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"155 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.72 A","at 50 °C / rated value":"14.24 A","at 55 °C / rated value":"13.76 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"from below","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695083&mlfb=5SV9316-7PK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7PK16/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV9316-7PK16?","answer":"The breaking capacity is 6 kA per both EN 60898 and IEC 60947-2, which covers standard residential and light commercial distribution board fault levels."},{"question":"What is the residual current type and rating?","answer":"It is Type A (sensitive to pulsating DC and AC residual currents) with a rated tripping fault current of 30 mA."},{"question":"How do I get current pricing and availability for 5SV9316-7PK16?","answer":"The part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-7PK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-7PK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}