{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV9316-7PK32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV9316-7PK32","canonicalUrl":"https://aoctrl.com/siemens/5SV9316-7PK32","factsUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7PK32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole, 32 A rated, 30 mA residual current, Type A, 6 kA breaking capacity, 1 MW unit width, current production.","salesMarkdown":"Depth is 77 mm, installation depth 70 mm, so it clears most shallow enclosures, but verify the gland plate clearance if the board is tight. Temperature derating is published: 32 A at 30 °C drops to 30.4 A at 40 °C, 29.44 A at 45 °C, 28.8 A at 50 °C, and 27.84 A at 55 °C. Supply connects from below (position of power supply cord), which is the usual European convention; verify if your board busbar arrangement expects top feed. IP20 with the distribution board installed and conductors connected — that's touch-proof once enclosed, not rated for wet or dusty environments. The silicon-free marking matters if this board sits in a paint shop or coating line where silicone outgassing causes adhesion failures. Touch protection is built in, so no additional finger-safe shrouds needed for the line-side terminals. The instantaneous design means no intentional time delay on the residual current element — it trips within the standard response time for Type A RCDs. If you need selectivity with downstream RCDs, you'll want a time-delayed (S-type) device upstream instead.","metaTitle":"Siemens SENTRON 5SV9316-7PK32 RCBO, 32 A, 30 mA, Type A","metaDescription":"Siemens SENTRON 5SV9316-7PK32 RCBO, 2-pole, 32 A rated, 30 mA residual current, Type A, 6 kA breaking capacity. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"32 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"155 g","at 30 °C / rated value":"32 A","at 40 °C / rated value":"30.4 A","at 45 °C / rated value":"29.44 A","at 50 °C / rated value":"28.8 A","at 55 °C / rated value":"27.84 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"from below","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05db08bf17e53a37e5c485dcffc27c74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695085&mlfb=5SV9316-7PK32","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV9316-7PK32/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV9316-7PK32?","answer":"6 kA per both EN 60898 and IEC 60947-2. That's the standard breaking capacity for domestic and light commercial RCBOs; verify your prospective fault current at the installation point stays under that."},{"question":"What does Type A residual current mean for 5SV9316-7PK32?","answer":"Type A detects sinusoidal AC fault currents and pulsating DC fault currents up to 6 mA smooth DC. That covers most single-phase electronic loads — VFDs, LED drivers, switched-mode power supplies — that generate half-wave or phase-angle fault signatures a plain AC type would miss."},{"question":"Where can I buy 5SV9316-7PK32?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."},{"question":"Will 5SV9316-7PK32 fit in a panel designed for 5SY3025-7KL?","answer":"Both are 18 mm wide (1 MW unit) DIN-rail devices, so the footprint is the same. But 5SV9316-7PK32 is a 2-pole RCBO (overcurrent + RCD combined) while 5SY3025-7KL is a single-pole MCB only — the wiring and function are different. You cannot simply swap one for the other without redesigning the circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV9316-7PK32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV9316-7PK32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}