{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4106-6-ZW07","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4106-6-ZW07","canonicalUrl":"https://aoctrl.com/siemens/5SY4106-6-ZW07","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4106-6-ZW07","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4106-6-ZW07 miniature circuit breaker, 1-pole, B characteristic, 10 kA (IEC 60898-1), 35 kA (IEC 60947-2), 18 mm width, 76 mm depth, IP20.","salesMarkdown":"It occupies one modular width unit (18 mm) on a DIN rail, with a 76 mm depth and 90 mm height — fits standard 1-module cutouts in SENTRON distribution boards or any 35 mm DIN-rail enclosure. The 10 kA rating under IEC 60898-1 is the standard for domestic and light commercial distribution; the 35 kA under IEC 60947-2 is the industrial rating that tells a panel builder this MCB can clear higher prospective fault currents in an industrial supply. Operating temperature range of -40 °C to 75 °C covers most outdoor and unheated plant environments, though the derating curve above 40 °C (max 95% RH at 55 °C, dropping to 35% at 75 °C) means the breaker's thermal trip may shift — factor that into the load calculation if the panel sits near a furnace or in direct sunlight. Installation depth is 70 mm (the body is 76 mm deep, but the 70 mm figure accounts for the rail and wiring space). Certified to IEC / EN 60898-1 (the general MCB standard for household and similar installations) and IEC / EN 60947-2 (the industrial circuit-breaker standard for higher fault levels). Also carries UL 1077 and CSA C22.2 No. 235 recognition — the 5 kA rating under UL 1077 is the North American supplementary-protector rating, which means it's accepted as a branch-circuit protective device in UL 508A industrial control panels when used within its marked interrupting rating.","metaTitle":"Siemens 5SY4106-6-ZW07 SENTRON MCB, 1P, B-Curve, 10 kA","metaDescription":"Siemens SENTRON 5SY4106-6-ZW07 miniature circuit breaker, 1-pole, B characteristic, 10 kA per IEC 60898-1. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY4106-6-ZW07","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 230/400 V 10kA, 1-pole, B, 6 A, D=70 mm Multi-Unit Packaging (96 Stück)","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"B","according to EN 60898 rated value":"10 kA","according to IEC 60947-2 rated value":"35 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"2.1 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/947d8862dee1e9610df18d25334280ca.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1558920&mlfb=5SY4106-6-ZW07"},"ai":{"faq":[{"question":"Where can I buy 5SY4106-6-ZW07 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"Will 5SY4106-6-ZW07 drop into a panel specified around 5SY4140-7 without rewiring?","answer":"Both are 1-pole SENTRON MCBs with the same 18 mm width and DIN-rail mounting, so the physical fit is identical. The difference is the tripping characteristic: 5SY4106-6-ZW07 is B-curve (3-5x In), while 5SY4140-7 is a different curve — check the existing panel's load type before swapping, as a B-curve may nuisance-trip on inductive loads that a C-curve would handle."},{"question":"What compliance documentation does Siemens provide for 5SY4106-6-ZW07?","answer":"The MCB carries IEC/EN 60898-1, IEC/EN 60947-2, UL 1077, and CSA C22.2 No. 235 certifications. It is halogen-free and silicon-free, which supports RoHS and REACH compliance declarations. Standard documentation includes the declaration of conformity and the datasheet with detailed ratings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4106-6-ZW07","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4106-6-ZW07 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}