{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4113-7CV","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4113-7CV","canonicalUrl":"https://aoctrl.com/siemens/5SY4113-7CV","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4113-7CV","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 5SY4113-7CV, 1-pole miniature circuit breaker, C-curve, 13 A rated, 15 kA breaking capacity per IEC 60947-2, 18 mm width.","salesMarkdown":"## MCB for panel protection — 13 A C-curve, 15 kA The Siemens 5SY4113-7CV is a 1-pole miniature circuit breaker with C-curve trip characteristic, rated 13 A at 35 °C and 250 V AC single-phase. ## Thermal derating and ambient constraints The 13 A rating holds at 35 °C; at 40 °C it derates to 11.56 A, and at 50 °C to 9.9 A. The operating range spans -40 °C to 75 °C, with humidity limits of 95% RH up to 55 °C, tapering to 35% RH at 75 °C. Mounting position is unrestricted — vertical, horizontal, or inverted — which simplifies layout in crowded sub-distribution boards. IP20 with conductors connected, so it's intended for enclosed panel use, not washdown areas.","metaTitle":"Siemens 5SY4113-7CV MCB 1P C 13A 15kA IEC 60947-2","metaDescription":"Siemens 5SY4113-7CV miniature circuit breaker, 1-pole C-curve 13 A, 15 kA breaking capacity per IEC 60947-2. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY4113-7CV","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60947-2","description":"MCB Icu=15KA 230/400V 1P C13","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"13 A","Installation Depth":"70 mm","Degree Of Pollution":"3","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","at 35 °C rated value":"13 A","at 40 °C rated value":"11.56 A","at 45 °C rated value":"10.76 A","at 50 °C rated value":"9.9 A","at 55 °C rated value":"8.98 A","according to EN 61346-2":"F","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","Supply Voltage Frequency Rated Value":"50/60 Hz","according to IEC 60947-2 rated value":"15 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","operating voltage at DC rated value maximum":"72 V","with single-phase operation at AC rated value":"250 V","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Switching Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b32595168c4f68d8b97a0de15ef76ea9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1531873&mlfb=5SY4113-7CV"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY4113-7CV?","answer":"15 kA per IEC 60947-2, which covers most commercial and light industrial sub-distribution applications."},{"question":"Where can I buy 5SY4113-7CV?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a binding offer."},{"question":"Does 5SY4113-7CV drop into a panel specified for 5SY4116-7CV?","answer":"Yes — both are 1-pole C-curve MCBs in the same 18 mm modular width with identical mounting and terminal layout. The difference is the current rating: 5SY4113-7CV is 13 A, 5SY4116-7CV is 16 A. No rewiring needed if the load is within 13 A."},{"question":"What compliance documentation does 5SY4113-7CV carry?","answer":"It is certified to IEC / EN 60947-2, halogen-free and silicon-free. The standard covers the breaking capacity and safety requirements for industrial and commercial installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4113-7CV","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4113-7CV when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}