{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4116-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4116-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY4116-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4116-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4116-7CC, 1-pole miniature circuit breaker, C-curve, 10 kA breaking capacity per EN 60898, 400 VAC, 1 MW.","salesMarkdown":"Rated breaking capacity is 10 kA at 400 VAC per EN 60898, and 5 kA at 440 VAC per UL 1077 / CSA C22.2 No.235. Mounting position is unrestricted, and the IP20 finger-safe enclosure (with conductors connected) suits enclosed panel use — not outdoor or washdown locations. ## Integration notes The quick-assembly fastening method means the breaker clips onto the DIN rail without tools; the combined terminals accept both busbar and conductor connections on the same screw clamp. Operating temperature range from -40 °C to +75 °C covers most industrial environments, but note the humidity derating: max 95% RH at 55 °C, dropping to 35% at 75 °C. If the panel sees sustained high-humidity and high-temperature conditions, factor that into the breaker's thermal performance. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — sufficient for most machine-mounted panels.","metaTitle":"Siemens 5SY4116-7CC SENTRON MCB, 1P C-Curve, 10 kA, 400 VAC","metaDescription":"Siemens 5SY4116-7CC SENTRON miniature circuit breaker, 1-pole, C-curve, 10 kA breaking capacity per EN 60898, 400 VAC. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY4116-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 10kA, 1-pole, C, 16A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"10 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.8 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b74589af2a3c5abd5b9cc99d2a3bd66a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=466879&mlfb=5SY4116-7CC"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY4116-7CC?","answer":"10 kA at 400 VAC per EN 60898, and 5 kA at 440 VAC per UL 1077 and CSA C22.2 No.235."},{"question":"Where can I buy 5SY4116-7CC?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 5SY4116-7CC?","answer":"The breaker carries ratings per EN 60898 and UL 1077 / CSA C22.2 No.235. The SENTRON series typically supports CE, UKCA, and EAC marking; specific declarations are available from the manufacturer on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4116-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4116-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}