{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4116-7CV","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4116-7CV","canonicalUrl":"https://aoctrl.com/siemens/5SY4116-7CV","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4116-7CV","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4 series MCB, 1-pole, tripping characteristic C, 16 A rated current, 15 kA breaking capacity per IEC 60947-2, order code 5SY4116-7CV.","salesMarkdown":"The Siemens 5SY4116-7CV is a SENTRON 5SY4-series miniature circuit breaker (MCB) rated at 16 A with a C tripping characteristic, single-pole construction, and a 15 kA breaking capacity tested to IEC / EN 60947-2. The 1-pole design switches only the phase; neutral is not switched. Rated for 230 V AC single-phase operation and 250 V AC maximum under single-phase conditions. Mountable in any position. Operating temperature range from -40 °C to 75 °C, with humidity derating: max 95% RH up to 55 °C, tapering to 35% RH at 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Power loss is 1.8 W per pole in hot operating state. Designed to IEC / EN 60947-2 for industrial applications. Halogen-free and silicon-free construction. Sealable for tamper-proof installation.","metaTitle":"Siemens 5SY4116-7CV SENTRON MCB, 1P C16, 15kA IEC 60947-2","metaDescription":"Siemens 5SY4116-7CV SENTRON miniature circuit breaker, 1-pole, C-curve, 16 A, 15 kA breaking capacity per IEC 60947-2. Current-production part, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY4116-7CV","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60947-2","description":"MCB Icu=15KA 230/400V 1P C16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Degree Of Pollution":"3","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","Supply Voltage Frequency Rated Value":"50/60 Hz","according to IEC 60947-2 rated value":"15 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","operating voltage at DC rated value maximum":"72 V","with single-phase operation at AC rated value":"250 V","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.8 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5e4868f435d85517362795be7b461efb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1531878&mlfb=5SY4116-7CV"},"ai":{"faq":[{"question":"Who supplies 5SY4116-7CV and how is it quoted?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock or price figures are listed on this page."},{"question":"What compliance documentation does Siemens provide for 5SY4116-7CV?","answer":"The breaker is designed to IEC / EN 60947-2, halogen-free and silicon-free, with IP20 protection. Standard documentation includes the declaration of conformity to the applicable EU directives (Low Voltage Directive, RoHS) and the manufacturer's test certificates. Specific documents such as the CE declaration or UL file number should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4116-7CV","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4116-7CV when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}