{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4116-8CC11","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4116-8CC11","canonicalUrl":"https://aoctrl.com/siemens/5SY4116-8CC11","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4116-8CC11","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4116-8CC11 miniature circuit breaker, 1-pole D-curve 16 A, 10 kA breaking capacity, 18 mm width, IP20.","salesMarkdown":"The Siemens 5SY4116-8CC11 is a SENTRON miniature circuit breaker rated 16 A at 400 V AC with a D tripping characteristic and a 10 kA breaking capacity per EN 60898. Breaking capacity at 10 kA is the standard domestic and light commercial fault level; if your prospective short-circuit current exceeds that, you need an upstream current-limiting device or a higher-rated breaker. ## Panel fit and environment","metaTitle":"Siemens 5SY4116-8CC11 SENTRON MCB, 1P D 16 A, 10 kA","metaDescription":"Siemens 5SY4116-8CC11 SENTRON miniature circuit breaker, 1-pole, D-curve, 16 A, 10 kA breaking capacity per EN 60898. IP20, 18 mm wide. Active lifecycle, available to order. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Solid":"0.75 ... 35 mm²","Width":"18 mm","Height":"90 mm","Sealable":"Yes","Stranded":"0.75 ... 35 mm²","Rated Value":"50/60 Hz","Halogen-Free":"Yes","Silicon-Free":"Yes","Mounting type":"Quick assembly system","During Storage":"-40 ... +75 °C","Number of poles":"1","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-40 ... +70 °C","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","at AC / rated value":"400 V","Overvoltage category":"III","Combined Terminal Top":"Yes","Design of the product":"For railway applications","Number of width units":"1","Number of poles / Note":"1P","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","Combined Terminal Bottom":"Yes","Suitability for operation":"Mechanical engineering / industry","Current / at AC / rated value":"16 A","Tripping characteristic class":"D","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"10 kA","Position / of power supply cord":"Any","Product feature / Touch protection":"Yes","Influence of the surrounding temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Tightening torque / with screw-type terminals":"2.5 ... 3.5 N·m","Product function / neutral conductor switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"440 V","Mechanical service life (switching cycles) / typical":"10 000","Tightening torque [lbf·in] / with screw-type terminals":"22 ... 31 lbf·in"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0d6dfe28493c87ec86a2666e38ab7167.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=408293&mlfb=5SY4116-8CC11","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4116-8CC11/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY4116-8CC11?","answer":"10 kA per EN 60898 at 400 V AC. That is the standard domestic and light commercial fault level."},{"question":"Where can I buy 5SY4116-8CC11?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 5SY4116-8CC11 drop into a panel specified for 5SY3132-6?","answer":"The 5SY4116-8CC11 is a 1-pole D-curve 16 A breaker; the 5SY3132-6 is a different pole count and characteristic. They share the same 18 mm width and DIN-rail mounting, but the tripping curve and current rating differ — verify the circuit requirements before substituting."},{"question":"What compliance documentation does this brand provide?","answer":"The SENTRON series carries EN 60898 certification for breaking capacity. The part is halogen-free and silicon-free, which supports RoHS and REACH compliance. Specific declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4116-8CC11","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4116-8CC11 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}