{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4125-6CC11","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4125-6CC11","canonicalUrl":"https://aoctrl.com/siemens/5SY4125-6CC11","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4125-6CC11","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4125-6CC11, 1-pole miniature circuit breaker, 25 A, B characteristic, 10 kA breaking capacity per EN 60898, 18 mm width.","salesMarkdown":"## Key ratings and what they mean for your panel The 25 A rating at 35 °C is the headline figure, but the derating curve is what matters when the breaker sits in a warm enclosure: at 40 °C it carries 22.98 A, at 50 °C it drops to 20.72 A, and at 60 °C it is down to 18.22 A. If your panel ambient runs above 35 °C, size the load to the derated value, not the nameplate. The B characteristic (3–5 × In magnetic trip) is standard for resistive and general-purpose loads where nuisance tripping from inrush is not a concern — lighting circuits, small transformers, and control power feeds are typical. The 10 kA breaking capacity per EN 60898 means it safely interrupts a fault current up to that level; for systems with higher prospective fault current, a current-limiting upstream device is needed. Energy limitation class 3 indicates the let-through energy is low enough to protect downstream equipment in most coordination schemes. ## Environmental and compliance notes Halogen-free and silicon-free construction matters in railway and aerospace applications where outgassing can damage sensitive contacts or optics. The sealable design allows the installer to lock the toggle position with a padlock or wire seal, preventing unauthorized operation on critical circuits. Touch protection is integrated on the terminals, so accidental contact during maintenance is minimized. The operating temperature range of -40 °C to 75 °C covers cold-start conditions in unheated substations and hot enclosures near machinery. Humidity limits are specified: 95% RH at 55 °C, derating to 35% RH at 75 °C — relevant for tropical or washdown environments where condensation is a risk.","metaTitle":"Siemens 5SY4125-6CC11 SENTRON MCB, 1P, 25 A, B Curve, 10 kA","metaDescription":"Siemens 5SY4125-6CC11 SENTRON miniature circuit breaker, 1-pole, 25 A, B characteristic, 10 kA per EN 60898. Active lifecycle, sourced to order. IP20, 18 mm wide.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8b3ae05eab47be009ddab9f4af14744f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=411112&mlfb=5SY4125-6CC11","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4125-6CC11/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4125-6CC11","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4125-6CC11 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}