{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4132-6CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4132-6CC","canonicalUrl":"https://aoctrl.com/siemens/5SY4132-6CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4132-6CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4132-6CC, 1-pole miniature circuit breaker, B-curve, 10 kA (EN 60898), 400 V AC, 1 MW, IP20.","salesMarkdown":"The Siemens SENTRON 5SY4132-6CC is a 1-pole miniature circuit breaker with a B tripping characteristic, rated 10 kA breaking capacity per EN 60898 at 400 V AC. That B-curve means it trips at 3–5× rated current — standard for protecting residential and light commercial wiring where inrush isn't a concern. For UL 1077 / CSA C22.2 No.235 installations, the rating drops to 5 kA. The 1-pole design switches the line conductor only; no neutral switching, so it's for single-phase branch circuits where the neutral is bonded elsewhere. Voltage range: rated 400 V AC for single-phase operation, with a maximum of 440 V AC in multi-phase or single-phase configurations. DC rating tops out at 72 V — useful for control circuits but not for 125 V DC battery banks. Frequency is 50/60 Hz, covering standard mains worldwide. Occupies 1 modular width unit (18 mm wide,), so it fits standard 18 mm-per-pole spacing. Mounting position is any — horizontal, vertical, upside-down; the B-curve and thermal-magnetic trip aren't orientation-sensitive. Sealable for tamper-proofing in metering or security applications. Halogen-free and silicon-free — relevant for clean-room or high-reliability environments where outgassing could contaminate optics or contacts.","metaTitle":"Siemens 5SY4132-6CC SENTRON MCB, 1P B-Curve, 10 kA, 400 V","metaDescription":"Siemens SENTRON 5SY4132-6CC miniature circuit breaker, 1-pole, B-curve, 10 kA breaking capacity per EN 60898, 400 V AC. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9409c3844d72ffdb463b8365a62f5a8f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=327904&mlfb=5SY4132-6CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4132-6CC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4132-6CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4132-6CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}