{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4202-6CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4202-6CC","canonicalUrl":"https://aoctrl.com/siemens/5SY4202-6CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4202-6CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4202-6CC miniature circuit breaker, 2 A, B-curve, 2-pole, 10 kA breaking capacity per EN 60898, 440 V AC, 50/60 Hz.","salesMarkdown":"The 5SY4202-6CC: The 2 A rating is the continuous current at 35 °C ambient; at 40 °C it derates to 1.88 A, at 45 °C to 1.82 A, at 50 °C to 1.75 A, and at 55 °C to 1.68 A. Operating temperature range -40 to 75 °C. Relative humidity derating: max 95% up to 55 °C, max 55% up to 70 °C, max 35% up to 75 °C. Halogen-free and silicon-free construction. Degree of pollution 3, overvoltage category III. Sealable for tamper-proof installations. Energy limitation class 3.","metaTitle":"Siemens 5SY4202-6CC SENTRON MCB, 2 A B-Curve, 2-Pole, 10 kA","metaDescription":"Siemens 5SY4202-6CC SENTRON miniature circuit breaker, 2 A rated, B-curve trip, 2-pole, 10 kA breaking capacity per EN 60898. Current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY4202-6CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 10kA, 2-pole, B, 2A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","at AC / rated value":"2 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","according to EN 61346-2":"F","at 35 °C / rated value":"2 A","at 40 °C / rated value":"1.88 A","at 45 °C / rated value":"1.82 A","at 50 °C / rated value":"1.75 A","at 55 °C / rated value":"1.68 A","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","Position / Of Power Supply Cord":"Any","according to EN 60898 / rated value":"10 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage / Of The Operating Voltage":"AC","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","vibration resistance / according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5b3dcebc7a9326eacdec3b1c72436a11.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=23801&mlfb=5SY4202-6CC"},"ai":{"faq":[{"question":"What is the depth of 5SY4202-6CC?","answer":"The depth is 76 mm, with an installation depth of 70 mm."},{"question":"What is the width of 5SY4202-6CC?","answer":"The width is 36 mm, which corresponds to 2 modular width units on a DIN rail."},{"question":"Where can I buy 5SY4202-6CC and how is it quoted?","answer":"The 5SY4202-6CC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation is available for 5SY4202-6CC?","answer":"The breaker is designed to EN 60898 (breaking capacity 10 kA) and IEC 81346-2 / EN 61346-2 designation F. It is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations should be requested at quote time."},{"question":"Will 5SY4202-6CC drop into a panel specified for 5SY7210-7CC?","answer":"Both are 2-pole SENTRON MCBs with the same 36 mm width and DIN-rail mounting, so mechanical fit is the same. However, the 5SY7210-7CC has a different current rating and curve — verify the specific electrical ratings before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4202-6CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4202-6CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}