{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4205-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4205-7","canonicalUrl":"https://aoctrl.com/siemens/5SY4205-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4205-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4205-7, 2-pole miniature circuit breaker, C-curve, 10 kA (EN 60898-1) / 35 kA (IEC 60947-2), 400 V AC, 36 mm wide.","salesMarkdown":"The Siemens 5SY4205-7 is a 2-pole SENTRON miniature circuit breaker with a C-curve trip characteristic, rated 10 kA breaking capacity per EN 60898-1 and 35 kA per IEC 60947-2 at 400 V AC. That dual rating means it covers both residential-distribution board specs (EN) and industrial panel fault-current requirements (IEC) — the 35 kA figure is the one that matters when you're feeding a motor control center or a cement plant distribution board with a high prospective short-circuit current. The C-curve trips at 5 to 10 times rated current, so it's sized for motor and transformer inrush without nuisance tripping on a cold start. ## Dust, heat, and vibration Rated for ambient temperatures from -40 °C to 75 °C, so it lives in a hot control room next to a kiln or a cold unheated substation without derating drama. Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz — that's enough to survive on a vibrating conveyor panel or a crusher-plant wall. IP20 with connected conductors means it's sealed against finger contact but not dust ingress; mount it inside an enclosure that eats the dust and runs. ## Panel fit and wiring Width is 36 mm (2 modular units), depth 76 mm, height 90 mm. Snaps onto DIN rail via the quick assembly system — no tools needed. Mounting position any, so you can lay it sideways in a shallow gland plate if needed. Combined terminals top and bottom accept supply from either end; neutral conductor switching is not built in (this is a 2-pole breaker switching both phases, not a switched-neutral device). Pollution degree 3, overvoltage category III — rated for the heat, not the office. ## DC and multi-phase capability Rated 15 kA at DC per IEC 60947-2, so it can also serve DC distribution in a solar combiner or a battery bank. Multi-phase operation at 440 V AC matches 480 V delta systems common in North American industrial panels. Single-phase operation also at 440 V AC. Frequency range 50/60 Hz — standard line frequency, no derating needed.","metaTitle":"Siemens 5SY4205-7 SENTRON MCB, 2P C-Curve, 10 kA, 76 mm","metaDescription":"Siemens 5SY4205-7 SENTRON miniature circuit breaker, 2-pole C-curve, 10 kA per EN 60898-1, 35 kA per IEC 60947-2. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7faebabd3c3f7fba8ef856943421792f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=326663&mlfb=5SY4205-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4205-7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4205-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4205-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}