{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4210-8CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4210-8CC","canonicalUrl":"https://aoctrl.com/siemens/5SY4210-8CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4210-8CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON miniature circuit breaker, 5SY4210-8CC, 2-pole, 10 A rated current at AC, D tripping characteristic, 10 kA breaking capacity per EN 60898, 50/60 Hz, 440 V rated voltage.","salesMarkdown":"## What the ratings mean for the panel The 5SY4210-8CC is a Siemens SENTRON miniature circuit breaker (MCB) with a D tripping characteristic, rated 10 A at AC and 10 kA breaking capacity per EN 60898. The D curve means it tolerates high inrush currents — typically 10 to 20 times the rated current — making it the right choice for motor circuits, transformers, or welding equipment where the start-up surge would nuisance-trip a B or C curve breaker. The 10 kA breaking capacity at 400 V ensures it safely interrupts a fault up to that level without cascading upstream, which is critical for selectivity in a distribution panel. Rated voltage is 440 V AC, 50/60 Hz, and the breaker is 2-pole (switches both line conductors). The 2-module-width housing (36 mm per module) snaps onto a DIN rail and fits standard SENTRON distribution boards. Operating temperature range is -40 °C to 75 °C, with a derating curve: at 40 °C the continuous current drops to 9.19 A, at 50 °C to 8.29 A, and at 55 °C to 7.81 A. In a warm enclosure, size the load accordingly or allow ventilation. ## Integration and compliance Mounts in any position on a DIN rail via the quick-assembly system. Depth is 76 mm, which leaves clearance behind a standard 80 mm deep enclosure. The IP20 rating (with connected conductors) means it is suitable for installation inside a closed panel, not for wet or dusty environments. Pollution degree 3 and overvoltage category III confirm it is rated for fixed industrial installations where transient overvoltages are expected. Sealable, halogen-free, and silicon-free construction. Touch protection is built in. Compliance documentation (RoHS, REACH, UL, IEC) is provided by Siemens with the product; the MCB is designed to EN 60898 and carries the relevant markings.","metaTitle":"Siemens SENTRON 5SY4210-8CC MCB, 10A D-curve, 2-pole, 10kA","metaDescription":"Siemens SENTRON 5SY4210-8CC miniature circuit breaker, 10A, D tripping characteristic, 2-pole, 10kA breaking capacity per EN 60898. Current lifecycle stage, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83e292235ccfa37a43d71e09223f84f1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=350315&mlfb=5SY4210-8CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4210-8CC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4210-8CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4210-8CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}