{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4213-8CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4213-8CC","canonicalUrl":"https://aoctrl.com/siemens/5SY4213-8CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4213-8CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4213-8CC, miniature circuit breaker, 2-pole, D-curve 13 A, 10 kA per EN 60898, 400 V AC, 2 MW.","salesMarkdown":"## D-curve 13 A — motor and transformer branch protection Breaking capacity hits 10 kA at 400 V AC per EN 60898, and 5 kA per UL 1077 / CSA C22.2 No.235 — enough for most industrial panel sub-feeders where fault current stays under those thresholds. Rated operating voltage is 400 V AC (440 V max multi- or single-phase), with a DC rating of 72 V max — so it's a pure AC branch breaker; don't spec it for a DC bus. ## Thermal and environmental limits Relative humidity tolerance is 95% at 55 °C, derating to 35% at 75 °C — fine for most indoor industrial environments, but not rated for condensing atmospheres. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — survives normal machine vibration; no special dampening needed in a standard control cabinet. Siemens designates this breaker for mechanical engineering and industry applications — it's the go-to D-curve 13 A 2P for OEM panel builders and machine builders.","metaTitle":"Siemens 5SY4213-8CC SENTRON MCB, 2P D 13A 10kA","metaDescription":"Siemens SENTRON 5SY4213-8CC miniature circuit breaker, 2-pole, D-curve, 13 A, 10 kA breaking capacity per EN 60898. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY4213-8CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 10kA, 2-pole, D, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"D","according to EN 60898 rated value":"10 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83d962ebe0872d751ad0364c7ca6d6e0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=316023&mlfb=5SY4213-8CC"},"ai":{"faq":[{"question":"Can the 5SY4213-8CC be used on a DC circuit?","answer":"Only up to 72 V DC maximum. This is primarily an AC-rated breaker; for higher DC voltages you'd need a DC-rated series like the Siemens 5SY7."},{"question":"What is the width of the 5SY4213-8CC?","answer":"36 mm, which is 2 modular width units on a standard DIN rail. Depth is 76 mm, installation depth 70 mm."},{"question":"Does the 5SY4213-8CC accept auxiliary contacts or shunt trips?","answer":"Yes, supplementary devices can be installed. The breaker has combined terminals top and bottom and is designed to accept Siemens 5SY-series add-on modules for remote signaling or undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4213-8CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4213-8CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}