{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4216-7CV","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4216-7CV","canonicalUrl":"https://aoctrl.com/siemens/5SY4216-7CV","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4216-7CV","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 5SY4 series, 2-pole miniature circuit breaker, 16 A rated current, C tripping characteristic, 15 kA breaking capacity per IEC 60947-2, 440 V AC, IP20.","salesMarkdown":"The 5SY4216-7CV: The 15 kA breaking capacity at 400 V AC per IEC 60947-2 means this MCB can safely interrupt a fault current up to 15 kA without welding its contacts or cascading failure upstream — critical for selectivity studies in industrial distribution boards. The 16 A rating is at 35 °C ambient; the part derates to 14.83 A at 40 °C, 14.21 A at 45 °C, 13.6 A at 50 °C, and 12.86 A at 55 °C. The operating temperature range is -40 to 75 °C, with humidity limits of 95% up to 55 °C, 55% up to 70 °C, and 35% up to 75 °C. Rated for 440 V AC multi-phase operation, with a DC maximum of 72 V. The 2-pole design does not switch the neutral conductor. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Designed to IEC / EN 60947-2. Halogen-free and silicon-free construction. Suitability for mechanical engineering and industry is stated by the manufacturer. The part is sealable for tamper-evident applications.","metaTitle":"5SY4216-7CV 2-Pole MCB, 16 A, C-Curve, 15 kA IEC 60947-2","metaDescription":"5SY4216-7CV miniature circuit breaker, 2-pole, 16 A, C characteristic, 15 kA breaking capacity per IEC 60947-2. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY4216-7CV","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60947-2","description":"MCB Icu=15KA 400V 2P C16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"16 A","Installation Depth":"70 mm","Degree Of Pollution":"3","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","at 35 °C rated value":"16 A","at 40 °C rated value":"14.83 A","at 45 °C rated value":"14.21 A","at 50 °C rated value":"13.6 A","at 55 °C rated value":"12.86 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","Supply Voltage Frequency Rated Value":"50/60 Hz","according to IEC 60947-2 rated value":"15 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.8 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e2b54af156a1f4a36717114ae5845861.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1531556&mlfb=5SY4216-7CV"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SY4216-7CV?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and stock levels are confirmed at quote time."},{"question":"What is the closest functional second-source for 5SY4216-7CV?","answer":"Within the same 5SY4 family, the 5SY4116-7CV is a 1-pole version of the same 16 A C-curve rating. For a 2-pole replacement, the 5SY4216-7CV is the direct fit — the 1-pole variant would require a separate neutral pole and different panel wiring."},{"question":"Will 5SY4216-7CV drop into a panel specified around 5SY4113-7CV without rewiring?","answer":"The 5SY4113-7CV is a 1-pole 13 A C-curve MCB. The 5SY4216-7CV is a 2-pole 16 A unit with double the width (36 mm vs 18 mm). It will not fit the same DIN-rail footprint without a wider slot and a different busbar arrangement. The terminal design and mounting method are identical, but the pole count and current rating differ."},{"question":"What compliance documentation does Siemens provide for 5SY4216-7CV?","answer":"The part is designed to IEC / EN 60947-2. It is halogen-free and silicon-free. For specific declarations (RoHS, REACH, UL file number), request the manufacturer's declaration of conformity or the CE declaration through the RFQ process — these are typically provided with the shipment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4216-7CV","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4216-7CV when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}