{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4240-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4240-7","canonicalUrl":"https://aoctrl.com/siemens/5SY4240-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4240-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4240-7, 2-pole miniature circuit breaker, C-curve, 10 kA (EN 60898-1) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC, 2 MW units wide, IP20.","salesMarkdown":"The 5SY4240-7 carries 10 kA per EN 60898-1, 15 kA per IEC 60947-2 at 400 V AC, and 15 kA per IEC 60947-2 at 60 V DC. For UL 1077 / CSA C22.2 No.235 installations it is rated 5 kA. That 15 kA IEC figure gives headroom for high-fault locations near transformers or large drives — a standard 10 kA MCB would be marginal there. The dual-standard rating means it is accepted in IEC panels (EN 60898-1 for residential/commercial, IEC 60947-2 for industrial) and UL-recognized component circuits (UL 1077) without needing a separate UL 489 listed breaker. Voltage rating: 400 V AC (single- or multi-phase operation up to 440 V AC), 60 V DC nominal with a maximum operating voltage of 72 V DC. The 2-pole design does not switch the neutral (neutral conductor switching: no), so it is intended for double-pole overcurrent protection on line and switched neutral in single-phase circuits, or as a two-pole device on a 2-wire DC circuit. The supply frequency is 50/60 Hz. ## Installation and environmental fit Mounts in any position via the quick assembly system (snap-on DIN rail). The temperature range is -40 °C to 75 °C, with humidity derating: max 95% RH up to 55 °C, 55% RH up to 70 °C, 35% RH up to 75 °C. Sealable terminals (sealable: yes) allow the panel builder to lock the cover after commissioning — common for utility metering or tenant sub-metering where tamper evidence is required. Combined terminal top and bottom (combined terminal top: yes, combined terminal bottom: yes) means each pole accepts both the incoming and outgoing conductor under the same screw, simplifying daisy-chaining.","metaTitle":"Siemens 5SY4240-7 SENTRON MCB, 2P C-Curve, 10kA/15kA","metaDescription":"Siemens 5SY4240-7 SENTRON miniature circuit breaker, 2-pole C-curve, 10 kA per EN 60898-1 / 15 kA per IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$30.48","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/474a0490eada33d5d42ed681a17fe366.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=508961&mlfb=5SY4240-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4240-7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4240-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4240-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}