{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4413-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4413-6","canonicalUrl":"https://aoctrl.com/siemens/5SY4413-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4413-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4413-6, 4-pole miniature circuit breaker, 13 A rated current, B tripping characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2) breaking capacity, 4 modular width units, depth 76 mm.","salesMarkdown":"The 5SY4413-6 snaps onto a standard DIN rail via the quick assembly system, occupying 4 modular width units (72 mm) with a depth of 76 mm and an installation depth of 70 mm. Rated 13 A at AC with a B tripping characteristic, the 5SY4413-6 delivers a breaking capacity of 10 kA per EN 60898-1 and 20 kA per IEC 60947-2 / UL1077 — the higher figure applies when the MCB is certified as a supplementary protector under UL 1077. The 20 kA rating per IEC 60947-2 gives selectivity headroom against downstream faults in industrial panel feeders, while the 10 kA per EN 60898-1 covers residential and commercial branch circuits. Rated 13 A at 35 °C ambient, the continuous current derates to 11.39 A at 60 °C — a 12% drop that must be factored into panel thermal budgets. The operating ambient range spans -40 °C to 75 °C, with the surrounding humidity limited to 95% up to 55 °C, 55% up to 70 °C, and 35% up to 75 °C.","metaTitle":"Siemens 5SY4413-6 SENTRON 4-Pole MCB, 13 A, B Curve","metaDescription":"Siemens 5SY4413-6 SENTRON 4-pole MCB, 13 A, B characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2) breaking capacity. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY4413-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 400 V 10kA, 4-pole, B, 13 A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","according to EN 61346-2":"F","at 35 °C / rated value":"13 A","at 40 °C / rated value":"12.48 A","at 45 °C / rated value":"12.22 A","at 50 °C / rated value":"11.95 A","at 55 °C / rated value":"11.67 A","at 60 °C / rated value":"11.39 A","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"4","Tripping Characteristic Class":"B","Position / Of Power Supply Cord":"Any","according to EN 60898 / rated value":"10 kA","according to IEC 60947-2 / rated value":"20 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage / Of The Operating Voltage":"AC","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","at DC / according to IEC 60947-2 / rated value":"15 kA","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","vibration resistance / according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$318.99","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/00db2d06381c4020fca93b0cba8d84dc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=394829&mlfb=5SY4413-6"},"ai":{"faq":[{"question":"Where can I buy the Siemens 5SY4413-6 and get a price?","answer":"The 5SY4413-6 is sourced to order against an RFQ through independent distribution channels."},{"question":"What is the breaking capacity of Siemens 5SY4413-6?","answer":"The breaking capacity is 10 kA per EN 60898-1 and 20 kA per IEC 60947-2 / UL1077, depending on the applicable standard for the installation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4413-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4413-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}