{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4502-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4502-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY4502-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4502-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4502-7CC miniature circuit breaker, 2 A, C characteristic, 1P+N, 2-pole, 10 kA per EN 60898, 2 MW units.","salesMarkdown":"The 5SY4502-7CC: Rated 2 A at 35 °C, but derates to 1.88 A at 40 °C, 1.82 A at 45 °C, 1.75 A at 50 °C, and 1.68 A at 55 °C. If your panel ambient runs 50 °C, that 2 A breaker is good for 1.75 A continuous — size up if the load is near the nameplate. The C curve means magnetic trip at 5–10× In (10–20 A), so it's suited for motor or transformer inrush where a B curve would nuisance-trip. The 10 kA SCCR per EN 60898 covers most industrial panel fault currents at 230/400 V. Snap-on 36 mm wide body (2 modular width units) with quick assembly system. Mounts in any position on standard DIN rail. Touch protection is integrated. Sealable design for lockout/tagout. Halogen-free and silicon-free construction — no outgassing concerns near sensitive contacts or optics in the same panel. Neutral conductor switching (1P+N) means the neutral is broken with the phase, which is required for some isolation schemes and avoids a floating neutral on the load side when the breaker is off.","metaTitle":"Siemens 5SY4502-7CC SENTRON MCB, 2A C-Curve, 1P+N, 10kA","metaDescription":"Siemens 5SY4502-7CC SENTRON miniature circuit breaker, 2A rated, C characteristic, 1P+N, 10kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/182a50d01cbd9092e34e243a6dd59b71.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=175775&mlfb=5SY4502-7CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4502-7CC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4502-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4502-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}