{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4513-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4513-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY4513-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4513-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4513-7CC, 1P+N miniature circuit breaker, 13 A rated, C tripping curve, 10 kA (EN 60898), 2 MW, IP20.","salesMarkdown":"## What this MCB does for a panel The Siemens SENTRON 5SY4513-7CC is a 1P+N miniature circuit breaker rated 13 A at 35 °C with a C tripping curve and a 10 kA breaking capacity tested to EN 60898. It switches the line and switches the neutral, so you get full isolation on both poles in a single 2-module-width package — no separate neutral block needed downstream. The C curve means it holds through moderate inrush — think motorized valves, small contactor coils, or a handful of LED drivers — without nuisance tripping, but it still clears fast on a hard short. ## Derating that matters at the panel The 13 A rating holds at 35 °C ambient. At 40 °C it derates to 11.95 A, at 45 °C to 11.38 A, at 50 °C to 10.78 A, and at 55 °C to 10.15 A (–). If your panel runs warm — say a packed enclosure with drives or transformers — size the load to the derated figure, not the catalog number. Humidity limits track the temperature: max 95% RH up to 55 °C, then dropping to 55% at 70 °C and 35% at 75 °C.","metaTitle":"Siemens 5SY4513-7CC SENTRON MCB, 13A C-Curve 1P+N 10kA","metaDescription":"Siemens 5SY4513-7CC SENTRON miniature circuit breaker, 13 A rated, C characteristic, 1P+N, 10 kA breaking capacity per EN 60898. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1ef7636a75a10e7dad3458cb15060ffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=23686&mlfb=5SY4513-7CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4513-7CC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4513-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4513-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}