{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4613-5","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4613-5","canonicalUrl":"https://aoctrl.com/siemens/5SY4613-5","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4613-5","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4613-5, 4-pole (3P+N) miniature circuit breaker, 13 A rated current, tripping characteristic A, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, IP20, 4 MW.","salesMarkdown":"## Integrator's note on the 5SY4613-5 The Siemens 5SY4613-5 is a 4-pole (3P+N) SENTRON miniature circuit breaker rated at 13 A with a tripping characteristic A. This means the magnetic trip operates at 2 to 3 times In, making it suitable for protecting semiconductor loads or long cable runs where inrush is minimal — not for standard motor starting. The 10 kA breaking capacity per EN 60898 covers domestic/commercial fault levels, while the 20 kA per IEC 60947-2 gives you headroom for industrial panel SCCR requirements. The 4 MW (72 mm) footprint is standard for a 4-pole MCB on a DIN rail. ## Thermal derating and environment Rated 13 A at 35 °C ambient, the 5SY4613-5 derates to 12.48 A at 40 °C, 12.22 A at 45 °C, 11.95 A at 50 °C, 11.67 A at 55 °C, and 11.39 A at 60 °C. If your panel runs hot — say 50 °C inside the enclosure — you lose about 1 A of headroom. The operating range spans -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, tapering to 35% at 75 °C. Pollution degree 3 (conductive pollution) means it's rated for industrial environments, not clean office air. ## Panel integration and compliance Mounts in any position on a DIN rail via the quick assembly system. Installation depth is 70 mm; overall depth 76 mm. Combined terminals top and bottom accept conductors without separate busbar connectors. Touch protection is built in. The part is halogen-free and silicon-free — relevant if the panel is in a clean room or semiconductor fab where outgassing matters. Overvoltage category III means it's rated for fixed installation downstream of the main distribution board. IP20 with connected conductors — fine inside a closed panel, not for wet locations.","metaTitle":"Siemens 5SY4613-5 SENTRON MCB, 4P, 13 A, Char. A, 10/20 kA","metaDescription":"Siemens 5SY4613-5 SENTRON miniature circuit breaker, 4-pole 3P+N, 13 A, tripping characteristic A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), IP20, current lifecycle stage, available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"4","Width":"72 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/91a53c72cd6653e82bfeaeb44298c0ac.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=46380&mlfb=5SY4613-5","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY4613-5/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4613-5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4613-5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}