{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4613-5","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4613-5","canonicalUrl":"https://aoctrl.com/siemens/5SY4613-5","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4613-5","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4613-5, 4-pole (3P+N) miniature circuit breaker, 13 A rated current, tripping characteristic A, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, IP20, 4 MW.","salesMarkdown":"## Integrator's note on the 5SY4613-5 The Siemens 5SY4613-5 is a 4-pole (3P+N) SENTRON miniature circuit breaker rated at 13 A with a tripping characteristic A. This means the magnetic trip operates at 2 to 3 times In, making it suitable for protecting semiconductor loads or long cable runs where inrush is minimal — not for standard motor starting. The 10 kA breaking capacity per EN 60898 covers domestic/commercial fault levels, while the 20 kA per IEC 60947-2 gives you headroom for industrial panel SCCR requirements. The 4 MW (72 mm) footprint is standard for a 4-pole MCB on a DIN rail. ## Thermal derating and environment Rated 13 A at 35 °C ambient, the 5SY4613-5 derates to 12.48 A at 40 °C, 12.22 A at 45 °C, 11.95 A at 50 °C, 11.67 A at 55 °C, and 11.39 A at 60 °C. If your panel runs hot — say 50 °C inside the enclosure — you lose about 1 A of headroom. The operating range spans -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, tapering to 35% at 75 °C. Pollution degree 3 (conductive pollution) means it's rated for industrial environments, not clean office air. ## Panel integration and compliance Mounts in any position on a DIN rail via the quick assembly system. Installation depth is 70 mm; overall depth 76 mm. Combined terminals top and bottom accept conductors without separate busbar connectors. Touch protection is built in. The part is halogen-free and silicon-free — relevant if the panel is in a clean room or semiconductor fab where outgassing matters. Overvoltage category III means it's rated for fixed installation downstream of the main distribution board. IP20 with connected conductors — fine inside a closed panel, not for wet locations.","metaTitle":"Siemens 5SY4613-5 SENTRON MCB, 4P, 13 A, Char. A, 10/20 kA","metaDescription":"Siemens 5SY4613-5 SENTRON miniature circuit breaker, 4-pole 3P+N, 13 A, tripping characteristic A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), IP20, current lifecycle stage, available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY4613-5","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 10kA, 3+N-pole, A, 13 A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"4","Type Of Voltage":"AC","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Number Of Poles / Note":"3P+N","acc. to DIN EN 61346-2":"F","at 35 °C / rated value":"13 A","at 40 °C / rated value":"12.48 A","at 45 °C / rated value":"12.22 A","at 50 °C / rated value":"11.95 A","at 55 °C / rated value":"11.67 A","at 60 °C / rated value":"11.39 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"4","Tripping Characteristic Class":"A","acc. to EN 60898 / rated value":"10 kA","Position / Of Power Supply Cord":"Any","acc. to IEC 60947-2 / rated value":"20 kA","Product Feature / Touch Protection":"Yes","Supply Voltage Frequency / Rated Value":"50/60 Hz","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at DC / acc. to IEC 60947-2 / rated value":"15 kA","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Function / Neutral Conductor Switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/91a53c72cd6653e82bfeaeb44298c0ac.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=46380&mlfb=5SY4613-5"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SY4613-5?","answer":"The 5SY4613-5 is rated at 10 kA per EN 60898 and 20 kA per IEC 60947-2. The higher IEC figure applies when the MCB is used in an industrial distribution board per that standard."},{"question":"What does tripping characteristic A mean on this MCB?","answer":"Characteristic A means the magnetic trip operates at 2 to 3 times the rated current (In). For the 5SY4613-5 at 13 A, that's a magnetic trip between 26 A and 39 A. This is designed for semiconductor protection or long cable protection, not motor starting."},{"question":"Will 5SY4613-5 drop into a panel specified around 5SY7210-7CC without rewiring?","answer":"No. The 5SY7210-7CC is a different pole/current configuration. The 5SY4613-5 is 4-pole (3P+N) at 13 A; verify the existing wiring and load requirements before substituting."},{"question":"Where can I buy the 5SY4613-5?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4613-5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4613-5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}