{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY4616-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY4616-7","canonicalUrl":"https://aoctrl.com/siemens/5SY4616-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY4616-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY4616-7 miniature circuit breaker, 4-pole (3P+N), C-curve, 10 kA per EN 60898 / 20 kA per IEC 60947-2, 400 V AC, 72 mm wide.","salesMarkdown":"## Integrator's spec recap — 5SY4616-7 The Siemens 5SY4616-7 is a 4-pole (3P+N) miniature circuit breaker from the SENTRON family, with a C-curve trip characteristic and a 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, and 15 kA at DC per IEC 60947-2. It is rated for 400 V AC (440 V max in multi-phase or single-phase operation) and 60 V DC (72 V max). The 10 kA rating under EN 60898 covers the residential and light commercial duty most panel builders encounter. For DC circuits, the 15 kA rating at 60 V (72 V max) covers battery banks and DC bus applications. Under UL 1077 and CSA C22.2 No. 235, the breaker carries a 5 kA rating — sufficient for North American supplementary protection applications. Snap-on DIN rail mount, 4 MW wide (72 mm). The supply cord can enter from any position (top or bottom feed). Ambient temperature range is -40 °C to 75 °C, with derating for humidity (95% at 55 °C, 55% at 70 °C, 35% at 75 °C). The energy limitation class is 3, meaning it limits let-through energy effectively for downstream equipment protection.","metaTitle":"Siemens 5SY4616-7 SENTRON MCB, 4P C-curve, 10/20 kA","metaDescription":"Siemens 5SY4616-7 SENTRON miniature circuit breaker, 4-pole, C-curve, 10 kA (EN 60898) / 20 kA (IEC 60947-2). Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY4616-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 400 V 10kA, 3+N-pole, C, 16A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P+N","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"10 kA","according to IEC 60947-2 rated value":"20 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$38.10","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fde57181f578cc0513c40018258091e8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=268065&mlfb=5SY4616-7"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY4616-7?","answer":"10 kA per EN 60898, 20 kA per IEC 60947-2 at 400 V AC, and 15 kA at 60 V DC per IEC 60947-2. Under UL 1077 it is rated 5 kA."},{"question":"What compliance documentation does Siemens provide for 5SY4616-7?","answer":"The breaker complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. It is halogen-free and silicon-free. The manufacturer provides declarations of conformity and test reports for these standards."},{"question":"Where can I buy 5SY4616-7 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY4616-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY4616-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}