{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY5114-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY5114-7","canonicalUrl":"https://aoctrl.com/siemens/5SY5114-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY5114-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, miniature circuit breaker, 5SY5114-7, 1-pole C-curve, 10 kA per IEC/EN 60898-2, 400 V AC / 220 V DC, 18 mm width.","salesMarkdown":"It's rated for universal current operation (AC/DC) and carries a 10 kA breaking capacity per IEC/EN 60898-2, with a DC rating of 10 kA at 220 V per EN 60898-2 and a higher 15 kA per IEC 60947-2 at DC. Rated operational voltage is 400 V AC (single- or multi-phase) and 220 V DC, with a maximum DC voltage of 250 V. This covers standard 230/400 V distribution panels and 220 V DC control circuits. Designed to IEC / EN 60898-2 and UL1077, meaning it's accepted for both IEC and UL-style panels — a dual-cert part that avoids a separate UL-listing requirement in mixed-spec jobs. Halogen-free and silicon-free construction. Width is 18 mm (1 modular unit), depth 76 mm, height 90 mm, installation depth 70 mm. Combined terminals top and bottom; neutral conductor not switched. Sealable. ## Sourcing and verification Each unit carries the Siemens SENTRON brand mark and a date code on the side. Verify the lot number against the manufacturer's traceability database if counterfeit risk is a concern — remarked parts in this class often have mismatched font on the rating plate or a missing UL logo.","metaTitle":"Siemens 5SY5114-7 SENTRON MCB, 1P C-curve 10kA, 400V AC","metaDescription":"Siemens 5SY5114-7 SENTRON miniature circuit breaker, 1-pole C-curve, 10kA breaking capacity per IEC/EN 60898-2, UL1077. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4df7fbdfa7d47eb1123360cb08475930.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=34866&mlfb=5SY5114-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY5114-7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY5114-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY5114-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}