{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY5125-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY5125-6","canonicalUrl":"https://aoctrl.com/siemens/5SY5125-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY5125-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY5125-6 miniature circuit breaker, 1-pole, B characteristic, 10 kA (IEC/EN 60898-2), 15 kA (IEC 60947-2), 400 V AC / 220 V DC, 1 MW, IP20, halogen-free, silicon-free.","salesMarkdown":"The Siemens 5SY5125-6 is a 1-pole SENTRON miniature circuit breaker with a B tripping characteristic, rated to break 10 kA per IEC/EN 60898-2 and 15 kA per IEC 60947-2 at DC. It handles 400 V AC (single or multi-phase) and up to 220 V DC, making it suitable for universal-current branch circuits in distribution boards. In a panel with mixed loads, a B-curve MCB avoids nuisance tripping on modest surges while still clearing fast on a hard fault. If your fault-current study shows available short-circuit current above 10 kA at the panel, the 15 kA DC rating under IEC 60947-2 gives extra headroom for DC circuits — a useful margin for battery-backed or solar-combiner applications. The IP20 rating applies only with connected conductors — treat the busbar area as live when the cover is off. ## Where it goes in the panel Mounting position is unrestricted — horizontal, vertical, or flat — which helps when you're packing breakers into a tight gland plate layout. Combined terminals at both top and bottom accept copper conductors without separate busbar clamps. Listed to IEC / EN 60898-2 for residential-style MCB duty and to UL 1077 for supplementary protection in North American panels. The halogen-free and silicon-free construction means no corrosive off-gassing during a fault — important for sealed enclosures housing sensitive electronics. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz, so it holds up on a machine skid or near a reciprocating compressor.","metaTitle":"Siemens 5SY5125-6 SENTRON MCB, 1P, B-Curve, 10kA IEC/EN 6089","metaDescription":"Siemens 5SY5125-6 SENTRON miniature circuit breaker, 1-pole, B characteristic, 10 kA per IEC/EN 60898-2, 15 kA per IEC 60947-2. UL 1077 listed. Current production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/36f90d1ae71c3d794899d23ea9ba80be.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=507632&mlfb=5SY5125-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY5125-6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY5125-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY5125-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}